Specifications

Page 26
ZONESENSE PLUS
OPERATION & PROGRAMMING
9 Appendix C: Simple Example Wiring Diagram of a Basic FACP
+ -
RS485
MONITORED
INPUTS
COM 1 2 3
+ Z1 - + Z2 - + Z3 - + Z4 - + Z5 - + Z6 - + Z7 - + Z8 -
DETECTOR ZONES
+1 - +2 - +3 - +4 - + -
ALARM
+ -
FAULT
N/O C N/C
ALARM
FAULT
N/O C N/C
24VDC OUT
+ -
RST BZ
EARTH
DISABLE
LAM
8 Way Remote
Relay Board
EOL 3K3
Maximum of 40
Devices per Zone
ALL Un-used Zones MUST be Individually
Terminated with an EOL
ALARM OUTPUTS
Comms
Link
3 Sec
Reset
Pulse
Note: Comms Link
is required when
only one Systems
Comms board
is used
EOL
Resistor
EOL
Resistor
EOL
Resistors
EOL Termination Values
Zone = 10uf, 3K3,
4K7, 6K8, 10K
Monitored O/P's = 10Kohms
CN8:27V In from CN4 of the P/S
CN10: 27V Out to Backpan Termination Boards
CN6 PSU Control from CN2 of the P/S
Current Limited to 25mA. and
Detector Removal Facility Available
Maximum 500mA / 24V
Monitored Open
Collector
30 mA O/P's
Voltage Free
Contacts 1A/30V
Monitored
24V 500mA
O/P
+24v / 100mA
0v
12v Batt
12v Batt
+
-
-
+
-BATT+
DC OUTPUT
OV +27V
GND
1
2
1
2
6
8
4
3
5
7
TO THERMISTOR
EXTENSIONS OF PIN 1
(TEMPSENSE RTN) AND PIN 6
(TEMPSENSE) OF RJ45
RJ 45 PINOUT CONNECTIONS
1.TEMP SENSE RTN
2.SUPPLY SENSE
3.PSU V ADJ
4.CHARGER ON
5.LOAD ON
6.TEMPSENSE
7.BATTERY V SENSE
8.OV
1 2 3
CN2
CN5
CN5
CN2
LED
CN4
CN3
Power Supply Unit ( PSU )
Rear of Main Card
Front of Main Card Illustrated External Cabling
Power Supply / Main Board Internal Wiring
Programmable
Un-programmable
RST / BZ O/P is Programmable
as a Reset or Buzzer but not both
Fault Input
Door Switch
MCP
ACF
Warn Sys
Bell
TB2
TB3
TB13
TB4
TB5
TB12
EOL
Resistor
Shield
Note: Bases are fitted with diodes if
the detector removal facilty is used
EOL
Resistor
ASE
Terminate all 3 I/P's
with EOL Resistor
TB14
IMPORTANT; ON COMPLETION OF THE INSTALLATION FILL IN THE CONFIGURATION LABEL