Specifications
Page 16
ZONESENSE PLUS
OPERATION & PROGRAMMING
Non Latch
Non Latch if set will initiate an alarm only when the Zone is in alarm.
SRESET 60
Resets the Zone 60 seconds after the Zone comes out of alarm.
Reminder: Press Cancel to return to the Zones Menu and then
Move Right to access the
Clock menu.
Clock
To set the day and time press Enter and the day will be highlighted. Use the Move Up or
Move Down keys to step through the days of the week, then the Move Right key to
access the hours and minutes. To access each digit use the Move Right and Move Left
keys and to increment each digit use the Move Up and Move Down keys. Press Enter to
set the time and thenMove Right To access the MCP Zone Menu.
MCP Zone
Press Enter to assign the MCP to a Zone using the Move Up and / or Move Down keys
to select the Zone, ( 1- 8 ) that the MCP will be assigned to then Enter to update the
Program.
Press Cancel to return to the MCP Zone menu and then Move Right to access the
Outputs Menu.
Outputs
To assign Zones that will activate the monitored outputs press Enter and a sub menu will be
made available for programming. The default condition for each output is all Zones will
activate all outputs. The sub menu consists off;
Outputs
Bell
Warn Sys
ACF
ASE
Alarm
BGD ALM1
BGD ALM2
RST/BZ
To move through the sub menu use the Move Right and Move Left keys. For each
output press Enter, then the Move Left and Move Right to select the Zones that will
operate or not operate that output. Pressing the Move Up key will set the Zone to activate
the output and the Move Down key will set the selected Zone so it does not activate the
output.
All 8 Zones Selected Zones 1,2,7 and 8 Selected
Press Enter to Update the Program then Cancel to return to the Sub Menu and the Move
Right and or Move Left keys to move through it. Repeat the above procedure to set or
change the other Outputs as required.
CLOCK
FR 11 : 21
MCP ZONE
2
PROGRAM
UPDATED
WARN SYS
12345678
WARN SYS
12........... 78