Specifications
Page 14
ZONESENSE PLUS
OPERATION & PROGRAMMING
If the PASSWORD is accepted the screen will display ACF TRIP RESET. Use the Right keys to
move through the menu to SYSTEM OR PROGRAM.
Note 1: The operator has 10 seconds to complete Password entry. Failure to enter the Password
in this time results in the panel reverting to the default screen.
Note 2: The System and Program Menus are not accessible if an Alarm condition exists even if
the correct Password is entered.
6.2 System
After entering the Level 3 Password and moving to the SYSTEM menu press Enter and the;
1. Zone ISOLATE LED’s will illuminate;
2. common ISOLATED LED will flash; and the
3. LCD will display;
SYSTEM DISABLED And then BUZZER
Ignoring Buzzer, Mimic and Code menus ( explained below ) use the Move Right or Move
Left keys to move through the menu and the Move Up key to set YES or Move Down key to
set No. Yes meaning the facility / board / card has been fitted to the FACP and will be
programmed in the Programming Menu, No meaning it has not been fitted and will not appear in
the Programming Menu.
Typical Screen examples of the System Menu
Buzzer
Earth Mon
Brigade
Relay Board
Fire Fan
Resound Y/N
Alarm Buzzer Y/N
Y/N
Y/N
Y/N
Y/N
Sndr Card
Ind Card
Switch
I/P Card
Mimic
Code
Y/N
Y/N
Y/N
Y/N
Set Number
AS4428
Buzzer is the only option that has a sub-menu where the operator is required to make a selection
from the options offered.
Buzzer
Press Enter to access the Sub – Menu then theMove Left orMove Right key to select
either; Resound, Alarm or Alarm Buzzer then Enter. Set the Resound, Alarm by using the
Move Up key to Yes (activate on alarm ) or Move Down key for No ( not activate on
alarm ).
Resound Set to YES Alarm Set to YES
SYSTEM
DISABLED
BUZZER
ERTH
NO
BRIGADE
YES
RLY CARD
YES
RESOUND
YES
ALARM
YES