Specifications

Page 13
ZONESENSE PLUS
OPERATION & PROGRAMMING
Main Control Board Outputs Isolates
Press Enter to access the Isolate Main Control Board Monitored Outputs sub-menus as
seen below
Bell
Warn Sys
ACF
ASE
Alarm
Fault
Use the Move Right or Move Left keys to select the required menu and the Move Up
key to Isolate or the Move Down key to active.
If the:
Bell is Isolated the External Bell LED will be illuminated.
Warning System is Isolated the Warning System LED will be illuminated.
ACF is Isolated the ACF Fault / Isolate LED will be illuminated.
ASE, Alarm or Fault Output is Isolated the common Isolated LED will be
illuminated.
Press Cancel to back out of the Isolate Menu to the Main Menu.
Move Right to Enter the PASSWORD for level 3 Access
Wait for the screen to return to ACF TRIP and use Move Right to scroll to the SYSTEM or
PROGRAM Menu
Reminder: Press ENTER at the end of each selection to update the program.
6 Level 3 Access Programming
Level 3 is a technical level that allows a technician to;
initialise the FACP so it is capable of recognising how the system is constructed;
and SYSTEM
program how it will present information as well as how it will react to a change of
state of an input and / or output. PROGRAM
6.1 Password Entry
Returning to Faults in the Main Menu, Move Right for Password Entry to Level 3. OR if entering
the programming from the Default Screen press the Move Left key to directly access from the
ACF Reset Menu.
Press Enter and a flashing cursor will appear below the word PASSWORD. By using the Move
up and Move down keys the number on the screen will be incremented accordingly. Once the
first password number has been set use the Move right key to move to the next number to be
set. This operation has to be repeated four times as the PASSWORD is a four digit code. If a
number is incorrect it can be changed by using the Move Left and Right keys to position the
cursor over the incorrect number. Once the four numbers have been set pressing Enter initiates
the verification of the PASSWORD that has been entered. An incorrect PASSWORD will be
displayed as REJECTED and return the operator to the first menu of Level 1 access.
Press Enter Enter Password Correct Password Entry
BELL
ISOLATED
BELL
Active
ENTER
PASSWORD
PASSWORD
0000
PASSWORD
ACCEPTED