Specifications
Page 12
ZONESENSE PLUS
OPERATION & PROGRAMMING
Battery Test
Press the Move Right and / or Move Left key to move to the Battery Test menu, Press
Enter and the Battery Test will commence, that is the Charger will be disconnected from the
battery and a dummy load placed across the battery for 60 seconds. The battery voltage
should be above that specified ( 23.5 volts ) at the end of the testing period, if not a FAILED
message is displayed.
Battery Test Underway Test Successful Battery Failure
Sounder Tests of each Sounder
Press the Move Right and / or Move Left key to move to the Sounder Test menu, press
Enter, then select the Sounder by using the Move Up and / or Move Down keys until the
desired Sounder number is displayed, press Enter to start the test and Cancel to turn it off.
Press Enter Sounder 6 Selected Enter to Start
Cancel to Stop
Back in the Main Menu From TEST Move Right to ISOLATES
5.2 Isolates
To display the number of Isolates press Enter to access the menus then Move Left or Move
Right to select the required menu. The number of isolates will be displayed for each step.
Zone [ Main Brd ]
Monitored Outputs
Relay [ Relay Brd ]
Sounder [ Sndr Brd ]
Zones 1 to 8 are
[ Main Brd ]
Relays 1 to 8 are
Sounders 1 to 8 are
Active or Isolated
Active or Isolated
Active or Isolated
Only available if relays and or sounders are installed
Bell
Warn Sys
ACF
ASE
Alarm
Fault
Note: The Relay and Sounder Isolate Menus are only displayed if the boards are installed in the
FACP and set to active in the System Menu.
Main Control Board Zone, Relay Board or Sounder Board Isolates
Press Enter and use the Move Left or Move Right keys to select the Zone, Relay or
Sounder number then the Move up to key isolate or Move Down key to make active
(set) the required Zone, Relay or Sounder.
Press Enter Select Zone Number set, Active or Isolated
Note: X denotes the Zone number, substitute Relay or Sounder for those menus.
If a Zone or Zones are Isolated the Isolate LED for that Zone and the common Isolated LED
will be illuminated. If a Relay or Relays, Sounder or Sounders are isolated only the common
Isolate LED will be illuminated. The Isolate can be deactivated by pressing ISOLATE / DE-
ISOLATE while in the Output menu or repeating the steps above to de-isolate (make Active)
individual Zones.
BATT TST
26.1
BATT TST
PASS
BATT TST
FAIL
SNDR TST
SNDR TST
6
ZONES
X ISOL'D
ZONE 1
Active
ZONE 1
Isolated