Specifications
Page 11
ZONESENSE PLUS
OPERATION & PROGRAMMING
Note: If a Zone has been programmed to be;
1. NON LATCHING the panel will only go into alarm for 5 seconds and then automatically
reset.
2. Self Resetting ( SREST 60) the panel will go into alarm for 60 seconds and then
automatically reset.
Fault Test of each Zone
Once the test is commenced the Buzzer will rapidly turn on and off and the common Fault
and Zone Fault LED’s will flash. Press Acknowledge, the Buzzer will be silenced and the
common Fault and Zone Fault LED’s will continue to flash. Press Reset to return the panel
to normal. The LCD will indicate the Fault Test has been implemented on the selected Zone.
Fault Test Zone 1 Screen
Walk Test
IMPORTANT: The Brigade, Agent Release and any other system specific signalling
should be ISOLATED prior to initiating this test.
A Walk Test, sets the Zone to Non latching and allows the technician to test detectors and
MCP’s on that Zone. When a detector or MCP is put into alarm the “Alarm Outputs” will
operate, the corresponding “Zone Alarm” LED will flash and the buzzer will sound.
The Zone will stay in Alarm until the MCP, or detector under test is reset or, the test is
aborted by pressing Cancel or, the test times out. The time out period can be set by
pressing Enter once the Zone has been selected and using the Move Up and / or Move
Down keys to select the required time for the test. The default time is 5 minutes but can be
adjusted from 1 to 20 minutes by again using the Move Up and / or Move Down keys to
select the required time and then pressing Enter.
Press Enter Enter Time Enter
In the TEST END screen the operator has ten ( 10 ) seconds to enter the time before the test
will commence OR, the test can be started by pressing Enter.
Only one zone at a time can be in test mode, all other zones will operate as normal.
The LCD will display which Zone is the in Walk Test mode.
Lamp Test
Press the Move Right and / or Move Left key to move to the Lamp Test menu, press
Enter and each LED on the panel will be sequentially turned on for one second and then off
again. The Buzzer will sound at the start and completion of the test.
Press Enter Indicates the Test Progress Test Successful
Note: The operator has to visually confirm each LED illuminates.
FLT TST
ZONE 1
WLK TST
ZONE 1
TEST END
5 mins
CANCEL
TO END
LAMP TST
LAMP >>>>>>
>>>>>>>>TST
TEST...............
COMPLETE