Specifications

Page 10
ZONESENSE PLUS
OPERATION & PROGRAMMING
Accessing information on 2 Faults
Press Enter Move Right key to scroll Enter
OR Enter to view detail
LCD Screen Examples of System Status Faults
System Fault Battery Fault Power Fault
SYSTEM FAULT LED flashing POWER FAULT LED POWER FAULT LED
POWER LED on POWER LED off
Note: FAULT LED will be flashing ( for all 3 FAULTS )
5 Level 2 Access
At this level the operator is expected to have under gone training so as to be able to;
test crucial elements of the system and; TEST
isolate dedicated facilities that may be in fault. ISOLATE
In the Main Menu From FAULTS Move Right for TEST
5.1 Tests
Press Enter to access the available menus
The available menus are;
Alarm Test
Fault Test
Walk Test
Lamp Test
Battery Test
Sounder Test
Note: The Sounder Test Menu is only displayed if it is installed and set to active in the System
Menu.
To initiate one of the above tests press the Move Right / Move Left key to move through the
menu. Press Enter, then select the Zone by using the Move Up and / or Move Down keys
until the desired Zone number is displayed, press Enter to start the test.
Alarm Test of each Zone
Once the test is commenced the Buzzer will turn on and off and the common Alarm and
Zone Alarm LED’s will flash. Press Acknowledge, the Buzzer will be silenced and the
common Alarm and Zone Alarm LED’s will be steady. Press Reset to return the panel to
normal. The LCD will indicate the alarm has occurred and then toggle to display the Zone
and descriptor of that Zone.
Alarm LCD Sequence
FAULTS
2 Flts
F 1 / 2
ZONE 7
F 2 / 2
ZONE 8
ZONE 7
OPEN CCT
ZONE 8
OPEN CCT
F 1 / 2
EXTERNAL
F 1 / 3
BATTERY
F 1 / 1
CHARGER
ALRM TST
ZONE 1
ALARM
OCCURRED
Z1 : LOBBY