ZONESENSE PLUS OPERATION & PROGRAMMING Table of Contents SECTION ............................................................................................... Page No Responding to an Alarm ............................................................................................................ 1 1 Introduction ..................................................................................................................... 2 2 Controls – Front Panel.............................................
ZONESENSE PLUS OPERATION & PROGRAMMING Responding To An Alarm 1. Indicators - Zone Alarm Indicator ( flashing ) - Common Alarm Indicator ( flashing ) - First Zone in Alarm is Displayed on LCD. Z7 ZONE SEVEN 2. To Isolate External Bell or To Isolate Warning System EXTERNAL ALARM Press ISOLATE WARNING SYSTEM Press 3. To Acknowledge Alarm 4. To Isolate Alarm ALARM LED goes steady ISOLATED LED will be illuminated ALARM Press ISOLATE ISOLATED Press ACK ISOLATE 5.
ZONESENSE PLUS 1 OPERATION & PROGRAMMING Introduction Using 3 levels of access the ZoneSense PLUS Fire Alarm Control Panel ( FACP ) is controlled and programmed through the keypad on the front panel. 2 Note: To assist in the programming process the screens or Menus presented to the operator are diagrammatically shown as an Appendix at the end of this document. Controls – Front Panel 2.
ZONESENSE PLUS OPERATION & PROGRAMMING Level3: ( Pre-commissioning Password factory set at 3333 ) Level 3 SYSTEM and PROGRAM menus can only be accessed by a set Level 3 password that can not be deleted. Panels fitted with a key switch have access to level 2 with the switch enabled and then 3 via the password. Without the key switch access to level 2 is by opening the door and then to level 3 via the password.
ZONESENSE PLUS 2.4 OPERATION & PROGRAMMING System Controls For the purposes of this explanation the following indicators perform these functions; Enter or Menu is used to access the various menus and sub-menus and update the program once the control settings have been set within a menu. MENU ENTER MENU ENTER Move Left allows the operator to move left through a menu or the options to be set. Move Right allows the operator to move right through a menu or the options to be set.
ZONESENSE PLUS EARTH FAULT OPERATION & PROGRAMMING Earth Fault – Yellow Is an indication only to warn of a fault to earth that may affect a mandatory function. A plug jumper facility is provided to disable the earth monitoring if necessary EXTERNAL ALARM FAULT External Bell Fault – Yellow Illuminates when an open or short circuit fault condition is detected on the external alarm circuit. WARNING SYSTEM FAULT Warning System Fault – Yellow Illuminated by a fault condition of the warning system output.
ZONESENSE PLUS OPERATION & PROGRAMMING ALARM ALARM ZONE 1 ZONE 2 ZONE 1 ZONE 3 ZONE 4 ZONE 3 ZONE 5 ZONE 6 FAULT / ISOLATE ZONE 8 4 ZONE FACP ZONE 7 ZONE 2 ZONE 4 FAULT / ISOLATE 8 ZONE FACP 2. Zone Fault / Isolate – Amber Illuminated by; a fault condition on an individual zone (flashing); isolating a zone/s, illuminated steady unless in fault, then flashes.
ZONESENSE PLUS 4 OPERATION & PROGRAMMING Level 1 Access Is a read only menu that allows the operator to reset latched Ancillary Control Facility outputs ( IF FITTED ) In the event an ancillary device trips out or is operated for some reason the latching control of the device has to be reset to re-establish normal functionality of that device. Press Enter to reset. The LCD will display the reset progress as seen below and then return to the Default Screen.
ZONESENSE PLUS OPERATION & PROGRAMMING Brigade Press Enter then Move Right or Move Left to view the Brigade screen. Press Enter then Move Right or Move Left to view the Status of the Alarm 1 & 2, Fault, Isolate and Battery Fail monitoring on the Brigade Board. ALARM OFF ISOLATE OFF BATTERY 27.2V ALARM OCCURRED ISOLATE ON CHARGER 27.2V Z2 : ZONE 4 SYSTEM 27V Sample Brigade Screen Relays Press Enter then Move Left or Move Right to select the required Relay (1 – 8).
ZONESENSE PLUS OPERATION & PROGRAMMING Sounders Press Enter then Move Left or Move Right to select the required Sounder (1–8). OR Press Move right to access Voltage. The LCD indicates if the selected Sounder Board output is; SOUNDER 2 ON / NOR SOUNDER 8 OFF / NOR SOUNDER 7 OFF / FLT Sample Sounder Screens Off and Normal, or Off and in Fault, or On and Normal, or On and in Fault, or Isolated and Normal, or Isolated and in Fault.
ZONESENSE PLUS OPERATION & PROGRAMMING Accessing information on 2 Faults F1/2 ZONE 7 FAULTS 2 Flts Press Enter F2/2 ZONE 8 Move Right key to scroll OR Enter to view detail Enter ZONE 8 OPEN CCT ZONE 7 OPEN CCT LCD Screen Examples of System Status Faults F1/3 BATTERY F1/2 EXTERNAL System Fault SYSTEM FAULT LED flashing Battery Fault POWER FAULT LED POWER LED on Note: FAULT LED will be flashing ( for all 3 FAULTS ) 5 Level 2 Access F1/1 CHARGER Power Fault POWER FAULT LED POWER
ZONESENSE PLUS OPERATION & PROGRAMMING Note: If a Zone has been programmed to be; 1. NON LATCHING the panel will only go into alarm for 5 seconds and then automatically reset. 2. Self Resetting ( SREST 60) the panel will go into alarm for 60 seconds and then automatically reset. Fault Test of each Zone Once the test is commenced the Buzzer will rapidly turn on and off and the common Fault and Zone Fault LED’s will flash.
ZONESENSE PLUS OPERATION & PROGRAMMING Battery Test Press the Move Right and / or Move Left key to move to the Battery Test menu, Press Enter and the Battery Test will commence, that is the Charger will be disconnected from the battery and a dummy load placed across the battery for 60 seconds. The battery voltage should be above that specified ( 23.5 volts ) at the end of the testing period, if not a FAILED message is displayed. BATT TST PASS BATT TST 26.
ZONESENSE PLUS OPERATION & PROGRAMMING Main Control Board Outputs Isolates Press Enter to access the Isolate – Main Control Board Monitored Outputs sub-menus as seen below Bell Warn Sys ACF ASE Alarm Fault Use the Move Right or Move Left keys to select the required menu and the Move Up key to Isolate or the Move Down key to active. BELL ISOLATED If the: BELL Active Bell is Isolated the External Bell LED will be illuminated.
ZONESENSE PLUS OPERATION & PROGRAMMING If the PASSWORD is accepted the screen will display ACF TRIP RESET. Use the Right keys to move through the menu to SYSTEM OR PROGRAM. Note 1: The operator has 10 seconds to complete Password entry. Failure to enter the Password in this time results in the panel reverting to the default screen. Note 2: The System and Program Menus are not accessible if an Alarm condition exists even if the correct Password is entered. 6.
ZONESENSE PLUS OPERATION & PROGRAMMING LED Annunciator Master ( LAM ) This tells the FACP how many LAMs are on the system hence how many to look for. Set the number by using the Move Down and / or Move Up keys to increment to the desired number 0 to 8 ( maximum of 8 ). LAM 8 Code Code is the National Standard the Panel complies with. This is factory set and can not be altered.
ZONESENSE PLUS OPERATION & PROGRAMMING Non Latch Non Latch if set will initiate an alarm only when the Zone is in alarm. SRESET 60 Resets the Zone 60 seconds after the Zone comes out of alarm. Reminder: Press Cancel to return to the Zones Menu and then Move Right to access the Clock menu. Clock To set the day and time press Enter and the day will be highlighted. Use the Move Up or Move Down keys to step through the days of the week, then the Move Right key to access the hours and minutes.
ZONESENSE PLUS OPERATION & PROGRAMMING Set the Reset / Buzzer output option so as the output acts as a Reset or Buzzer function as per the system design configuration. RST / BZ RESET Screen Showing the Output Set to Reset If the output is used set as a Reset or Buzzer function by using the Move Up for Buzzer or Move Down keys for Reset.
ZONESENSE PLUS OPERATION & PROGRAMMING Fire Fan FAN 2 The sub menu consists of; Alarm For: Inhibit Alarm Function Latch ACF Isolate Inhibit Press Enter then use the Move Right and / or Move Left keys to select the Fire Fan that will be controlled by the selected functions in the sub - menu . Press Enter to access the sub – menu then Move Right and /or Move Left keys to toggle through the sub - menu structure.
ZONESENSE PLUS OPERATION & PROGRAMMING ACF Isolate Press Enter and the cursor will flash over YES or NO and then the Move Up or Move Down keys to set the card to be isolated or not isolated by the ACF key, that is Yes or No. ACF ISOL NO ACF ISOL YES Press Enter to update the Program and Cancel to back out of the Menu. Sounders Press Enter then use the Move Right and Move Left keys to select a sounder.
ZONESENSE PLUS OPERATION & PROGRAMMING Zone Labels To name the Zones press Enter then the Move Right and / or the Move Left keys to select a Zone. Press Enter and use the Move left and / or Move Right keys to move the cursor through the structure of the word and the Move Up and Move Down keys to move through the alphabet. Z LABELS ZONE 1 Z1 : LOBBY Press Enter to update each Program and Cancel to back out of the Menu.
ZONESENSE PLUS 7 OPERATION & PROGRAMMING Appendix A: AS 4428 Menu Structure & Programming STATUS FAULTS TESTS ISOLATE SYSTEM PROGRAM Status MENU ENTER STATUS PRESS THESE KEYS TO SET YES / NO, OFF / ON, OFF NORMAL PRESS ENTER TO GO TO SUB MENU, SET MENU OR UPDATE PROGRAM MENU ENTER RELAYS BRIGADE OUTPUTS MENU ENTER MENU ENTER PRESS CANCEL AT ANY TIME TO BACK OUT OF THE MENU PRESS: MOVE FORWARD OR BACKWARD THROUGH THE MENU CANCEL MENU ENTER CANCEL SOUNDERS FIRE FAN MENU ENTER MENU E
ZONESENSE PLUS OPERATION & PROGRAMMING Test MENU ENTER LEGEND: TEST MENU ENTER MENU ENTER ALARM T E ST PRESS ENTER TO START TEST PRESS TO INCREMENT UP DOWN ZONE NUMBER TO BE TESTED ZONE 2 T E ST ZONE 1 T E ST MENU ENTER ZONE 4 T E ST ZONE 3 T E ST MENU ENTER ZONE 1 T E ST ZONE 2 T E ST ZONE 3 T E ST ZONE 4 T E ST WALK T E ST MENU ENTER ZONE 1 T E ST ZONE 2 T E ST ZONE 3 T E ST ZONE 4 T E ST MENU ENTER MENU ENTER LAMP>>>> TEST>>>> ZONE 6 ACTIVE ZONE 5 T E ST ZONE 6 T E ST ZONE 6
ZONESENSE PLUS OPERATION & PROGRAMMING System ( Password required ) E NTER MENU PASSWORD ENTER SYSTEM MENU ENTER BUZZER FACTORY DEFAULT PASSWORD IS 3333 EXAMPLE OF ENTERING PASSWORD 3333 PASSWORD 3000 PASSWORD 3300 PASSWORD 3330 PASSWORD 3333 ALARM YES / NO RESOUND YES / NO EXAMPLE SET RESOUND TO YES THEN MOVE TO ALARM YES EARTH MON YES / NO MENU ENTER MENU ENTER PASSWORD 0000 MENU ENTER UPDATE PROGRAM MOVE TO ALARM YES / NO BRIGADE YES / NO RELAYS YES/ NO FIRE FAN YES / NO NOTES: TO
ZONESENSE PLUS OPERATION & PROGRAMMING Program Agent Notes: If only one trigger zone is allocated a zone then the system will be activated by one zone only. Any trigger zone may be allocated to any zone. However when a trigger zone has been allocated eg T1 to zone 1 then only the remaining trigger zones T2, T3 or T4 are each available to be allocated one of the remaining detector zones.
ZONESENSE PLUS 8 OPERATION & PROGRAMMING Appendix B: AS4428 ABS Front Panel Configuration Labelling ZONE CONFIGURATION 1 NORM / AVF / NON / SELF / AT1 / AT2 / AT3 / AT4 NORM / AVF / NON / SELF / AT1 / AT2 / AT3 / AT4 2 3 NORM / AVF / NON / SELF / AT1 / AT2 / AT3 / AT4 4 NORM / AVF / NON / SELF / AT1 / AT2 / AT3 / AT4 5 NORM / AVF / NON / SELF / AT1 / AT2 / AT3 / AT4 NORM / AVF / NON / SELF / AT1 / AT2 / AT3 / AT4 6 7 NORM / AVF / NON / SELF / AT1 / AT2 / AT3 / AT4 8 NORM / AVF / NON / SELF / AT1 / AT2 /
ZONESENSE PLUS Appendix C: Simple Example Wiring Diagram of a Basic FACP Terminate all 3 I/P's Fault Input with EOL Resistor EOL Termination Values Zone = 10uf, 3K3, 4K7, 6K8, 10K Monitored O/P's = 10Kohms Maximum of 40 Devices per Zone Front of Main Card Illustrated External Cabling EOL Resistor EOL Resistor MCP EOL Resistor EOL 3K3 Note: Bases are fitted with diodes if the detector removal facilty is used LAM 8 Way Remote Relay Board EOL Resistor ALL Un-used Zones MUST be Individually Terminate
UNCONTROLLED DOCUMENT NOTE: Due to AMPAC’s commitment to continuous improvement specifications may change without notice.