Installation & Commissioning of Control & Monitoring Add On’s PLUS ZoneSense SYSTE M STATU S P O WER POWER FAULT SYSTEM FAULT EARTH FAULT ALARMS STATUS FIRE FIRE OUTPUT STATUS ZONE 1 FAULT OUPUT STATUS ZONE 5 ZONE 2 ANCILLARY OUTPUT DISABLED TEST ZONE 6 ZONE 3 AMPAC ZONE 7 ZONE 4 FIRE OUTPUT ON SYSTEM IS NORMAL ZONE 8 FAULT / DISABLED/TEST N ORMAL DELAY ACTIVE ALARMS FI RE FAULT DISABLED OVERRIDE SI LENCE R ESO UND SILENCE BUZZER R ESET EVACUATE ENABLE M ENU I E NTE R CANCEL
Installation & Commissioning of Control & Monitoring Add On’s Table of Contents 1 About This Manual............................................................................................... 2 1.1 1.2 1.3 1.4 2 Internal Communications Connector (RS485).................................................4 Programming ......................................................................................................4 Installation and Wiring of Add On Cards and Boards .................................
Installation & Commissioning of Control & Monitoring Add On’s 1 About This Manual 1.1 Purpose This manual is an instructional tool for the installation and commissioning, of add on ancillary cards, modules and boards that can be fitted to the ZoneSense PLUS Fire Alarm Control Panel (FACP) and should be read in conjunction with the main Installation and Commissioning Manual. 1.
Installation & Commissioning of Control & Monitoring Add On’s 1.4 PCB Removal / Replacement If the PCB’s have to be removed the following precautions should be observed; 2 Note: 1. Removing the door will provide better access to the boards and ensure the hinges are not accidentally stressed. 2. Personal anti- static procedures must be followed. 3.
Installation & Commissioning of Control & Monitoring Add On’s 3 Adding Control and Monitoring Facilities A combination of one of each type of board / card, but not all of them, can be mounted on the back pan or the front panel of the FACP to provide additional features to a standard panel. All board inputs or outputs are programmable to any combination of zones.
Installation & Commissioning of Control & Monitoring Add On’s 4.1 Address Setting and Terminating the Communications Bus Address Setting ( SW1 ) Except for the LED Mimics in ZoneSense PLUS FACP’s there can only be one (1) Board / Card of each type so the address on each board is set to 1. Note: There can be up to 8 remote LED Mimics so the address of each is set from 1-8 depending on the number Mimics in the system. The information displayed at each location will be identical.
Installation & Commissioning of Control & Monitoring Add On’s 4.2 Input Board BRD25SIPB Description The Input Board makes provision for 16 voltage free contacts to be terminated to 16 optically coupled inputs. Its application is primarily for the monitoring of controlled ancillary equipment or to initiate an action / event due to a change of state from what is accepted as the norm. Connectors CN1 Is designated as the input Comms . CN2 Is designated as the output Comms to the next board.
Installation & Commissioning of Control & Monitoring Add On’s Relay Board ( Remote ) BRD25EWRB - B Note#2: In a system there can only be either a remote OR an internal board, not both. COM N/C O/P 2 N/0 TB1 COM N/C N/0 TB2 O/P 3 COM N/C N/0 TB3 O/P 4 COM N/C O/P 5 N/0 TB4 COM N/C N/0 TB5 O/P 6 N/C COM TB6 N/0 O/P 7 N/C COM TB7 N/0 O/P 8 COM N/C TB8 rev.
Installation & Commissioning of Control & Monitoring Add On’s 4.5 Fan Termination Board BRD25FTB The Fan Termination Board interfaces between the Fire Fan Module and the plant/equipment it controls via the 24 volt 250mA Start, Stop, current limited, relay outputs and monitor inputs. Programmable monitoring of the field equipment is achieved using 0 volts as an input level to indicate run, fault and stop conditions of that equipment.
Installation & Commissioning of Control & Monitoring Add On’s 4.7 Switch and Indicator Card BRD25GIB - B This Card can effectively perform 2 different functions. Firstly the indicators monitor the first 8 inputs of the 16 Way Input Termination Board while secondly the switches can be programmed to manually operate a specific relay in the system. Quiescent Current: 3.
Installation & Commissioning of Control & Monitoring Add On’s 4.9 Zone Mimic Indicator Card ( Externally Powered. ) BRD25GIB -C The externally powered Zone Mimic Indicator Card operates in the same way as does the internally powered version. The only difference is that the 27 volt power supply is independent of the FACP.
Installation & Commissioning of Control & Monitoring Add On’s 4.11 Sounder Board BRD25SOPB -A The Sounder Board expands the number of sounders that can be used on an FACP to 8. Each solid state output is rated at 24VDC / 500mA. and requires a 10KΩ End of Line (EOL) resistor regardless whether or not a sounder is wired to the circuit. Quiescent Current: 5.
Installation & Commissioning of Control & Monitoring Add On’s Disabled Mode Disabled mode is selected by placing the keyswitch at the Agent Release Module in the Disabled position. This electrically isolates the activation circuit, and results in the following: ¾ Disabled indicators at the Agent Release Module and Local Control Station are lit. ¾ Agent Release Module and Local Control Station buzzers sound. ¾ No automatic releases can be commenced. ¾ System inoperative output is activated.
Installation & Commissioning of Control & Monitoring Add On’s When the second zone goes into alarm, then the following steps are followed 9 Auto release activated LED on the Agent Release Module and Local Control Station goes steady 9 Stage 2 outputs are pulsed during the pre-release delay to +24VDC 9 Start optional pre-release delay. (Selected via FACP on-site programming). 9 Upon expiration of the delay, activate the selected activation circuit and stage 2 outputs becomes steady.
Installation & Commissioning of Control & Monitoring Add On’s Isolation If the trigger zones are isolated by the FACP, then the trigger zone isolated indicator at the Agent Release Module and Local Control Station is illuminated, and the system inoperative output is operated. Disablement of the Trigger Zones If the trigger zones are disabled by the FACP, then the isolate indicator at the FACP is illuminated and the system inoperative output is operated. 5.
Installation & Commissioning of Control & Monitoring Add On’s Agent Release Module PCB Layout The PCB is fitted with two 2 x RJ45 connectors CN6 & 7 for power (27VDC) and communications (RS485) for communications between the Module and the FACP Main Card. Quiescent Current: 28.
Installation & Commissioning of Control & Monitoring Add On’s 5.4 Common Agent Release Module and Local Control Station Indicators MANUAL RELEASE ACTIVATED Manual Release Activated Red in colour. Lit when a manual agent release sequence has commenced. This can be instigated from the Agent Release Card and Local Control Station. AUTO RELEASE ACTIVATED Auto Release Activated Red in colour. Lit when a automatic agent release sequence has commenced.
Installation & Commissioning of Control & Monitoring Add On’s Local Control Station Terminal Blocks TB1 & TB2 TB2 Terminal 1 2 3 4 5 6 7 8 Assignment RS485 + In RS485 - In RS485 Common RS485 + Out RS485 - Out RS485 Common Interlock+ Interlock- TB1 Terminal 1 2 3 4 Assignment +27V In 0V In +27V Out 0V Out Quiescent Current: 18.5mA Local Control Station Layout The Comms line is RS485 between the Local Control Station and the Termination Board.
Installation & Commissioning of Control & Monitoring Add On’s The Agent Release Termination Board interfaces to the; 1. The FACP via CN1, CN2 continuing the RS485 communications bus if required. LK1 is inserted if this is the last backpan board on the bus. 2. LCS’s ( up to 4 ) via TB1. LK1 is inserted in the last board in the RS485 Bus 3. Monitored Inputs: via TB2.
Installation & Commissioning of Control & Monitoring Add On’s Solenoid & Metron This input relies on N/O or N/C relay contacts used in conjunction with 22KΩ EOL and 4K7Ω series resistors. The type of agent release mechanism and contacts used has to be set in the Programming Menu for the input to function as per the manufacturers specifications and be in accordance with the relevant Standard.
Installation & Commissioning of Control & Monitoring Add On’s 6 Appendix: Adding to the System Menu & Programming In this example 1 Input Board, 1 Relay Board and 1 Sounder Board will be added to the system. The Display and Zone Labels will then be edited. Step 1: Go to the SYSTEM MENU and then follow the procedure as set out below.
Installation & Commissioning of Control & Monitoring Add On’s Step 2 LEGEND: PROGRAM ACF ISOALTE PRESS ACF TO ISOLATE CIRCUITS EXTERNAL TO FACP MENU ENTER MENU ENTER ACF ISOALTE ZONES CANCEL PRESS CANCEL AT ANY TIME TO BACK OUT OF THE MENU CANCEL MENU ENTER PRESS ENTER TO GO TO SUB MENU, SET MENU OR UPDATE PROGRAM PRESS MOVE FORWARD / BACKWARD THROUGH THE MENU PRESS MOVE FORWARD THROUGH THE MENU CLOCK MCP ZONE Z# OUTPUTS IN THIS EXAMPLE RELAY 3 IS ACTIVATED BY ZONES 1,4 OR 8 WHEN IN ALARM OR
Installation & Commissioning of Control & Monitoring Add On’s 7 Status and Programming Screens The following shows all the screens that are possible in the FACP and how to navigate through them. I f a screen is not available it means that option has not been installed or is not available to the model in use. Operating Main Menu STATUS 7.
Installation & Commissioning of Control & Monitoring Add On’s 7.
Installation & Commissioning of Control & Monitoring Add On’s 7.
Installation & Commissioning of Control & Monitoring Add On’s AUSTRALIA AMPAC TECHNOLOGIES PTY LTD EUROPE AMPAC EUROPE LTD. NEW ZEALAND AMPAC INDUSTRIES LTD. 97 Walters Drive Osborne Park 6017 Western Australia Unit 1, Norden Court, Alan Ramsbottom Way Great Harwood, Blackburn England BB6 7UR Unit 4 101 Diana Drive Glenfield, Auckland New Zealand Tel: 61 8 9242 3333 Fax: 61 8 9242 3334 Email: info@ampac.net Tel: 44 (0) 1254 880 201 Fax: 44 (0) 1254 880 202 Email: info.eu@ampac.