Specifications
Page 87 
FIREFINDER SERIES II  INSTALLATION,  COMMISSIONING  & 
OPERATION 
In the above example Card 1 & 2; 
  Are active 
  Are situated in the factory floor area 8 
  Will display all Alarms 
  Will not display any Faults, and 
  Will not display any Disables 
Card 3 
  Is active 
  Is situated in the stores area 
  Will display all Alarms 
  Will display any Faults, and 
  Will not display any Disables 
Card 4 & 5 
Are active 
  Are situated in the security areas 
  Will display all Alarms 
  Will display any Faults, and 
  Will display any Disables 
14.10  Trouble Shooting Chart 
Problem 
Solution 
Normal Supply LED not illuminated 
Check supply voltage it should be set to 27.2VDC. 
Nominal fault voltages are - Low  = (<18VDC) 
High = (> 28VDC ) 
FACP Earth Fault LED illuminated 
Check all input  and output cabling and  wiring assemblies 
for short to ground 
FACP System Fault LED illuminated 
Ensure correct panel configuration 
Check all connections for loose wiring 
FACP  Warning System Fault LED 
illuminated 
Check correct E.O.L is fitted 
Check wiring is connected correctly 
RS485  Communication  Bus  not 
working 
Refer FACP LCD. This may identify where there is a break 
in the communication line 
Check the SmartTerminal Diagnostic Config LED is flashing. 
If  not  the  FACP  is  not  communicating  with  the 
SmartTerminal. Check the RS485 cabling. 
If flashing check the SmartTerminal’s address. 