Specifications
Page 79
FIREFINDER SERIES II INSTALLATION, COMMISSIONING &
OPERATION
14.2 LCD Screen Format
There are 3 events that can be reported and displayed by SmartTerminal. The types of event are;
Alarm
Faults and
Isolates.
The types of events are only associated with sensors and detectors hence faults associated with
modules, loops O/C – S/C, power supplies and so forth are not reported on the LCD.
The SmartTerminal has front panel indicators for each type of event. When SmartTerminal is
configured not to report a type of event and that event type is present (and the corresponding front
panel indicator is illuminated on the SmartTerminal), then a standard information screen is
displayed on the LCD stating the system is not normal and the operator should see the FACP.
Alarm: If configured the screen format for reporting loop / sensor / zone fire condition is:
Device descriptor (up to 33 characters) Type Descriptor (up to 6 characters)
Loop address and zone number(Lxx Syyy.zz Zwww) current device status
Date and Time of occurrence (DD/MM/YYYY HH:MM:SS)
Alarm sequence number ( Device Alarms nnn of nnn)
Fault: If configured the screen format for reporting loop / sensor / zone fault condition is:
Device descriptor (up to 33 characters) Type Descriptor (up to 6 characters)
Loop address and zone number(Lxx Syyy.zz Zwww) current device status
Fault sequence number ( Device Fault nnn of nnn)
Note: The fault types only relate to devices.
In the event of a loss of communications, for a period of greater than 15 seconds the SmartTerminal
will default to the No Communications screen. The format for this screen is:
No Communication
Device Isolate / Disables: If configured the screen format for reporting loop / sensor / zone disable
condition is:
Loop address and zone number(Lxx Syyy.zz Zwww) current device status
Isolate / Disable sequence number ( Device Fault nnn of nnn)
Device descriptor (up to 33 characters) Type Descriptor (up to 6 characters)
Pre-alarm: If configured the screen format for reporting loop / sensor / zone Pre-alarm condition is:
Pre-alarm descriptor (up to 15 characters)
Pre-alarm sequence number ( Device Pre-alarms nnn of nnn)
Loop address and zone number(Lxx Syyy.zz Zwww)