Specifications
Page 78
FIREFINDER SERIES II INSTALLATION, COMMISSIONING &
OPERATION
Key Switch Controls enable key switch. = OFF, = ON
Access level 1 (OFF) By Default. Only the Acknowledge, previous and next front panel controls are
operative. All other controls operate in access level two.
Access level 2 (ON) is entered when the key-switch is in the ENABLED position.
Buzzer
The Buzzer is activated under the following conditions and can be silenced by pressing the
Acknowledge (ACK) control locally or on the FACP.
Alarm condition
Devices – missing, out of calibration, wrong type, reporting an internal error
Loops – short circuit or open circuit
Monitored inputs and outputs on loop devices are in fault
Sounders – missing, wrong type or reporting an internal error
Modules within the panel – missing, wrong type or hardware error
Main and / or secondary power supply fault
POWER
(Green) Illuminated to show the presence of power. Flashes when mains
has failed
POWER FAULT
(Yellow) Illuminated when there is a fault with the power supply. Fault can
be no mains, high charger voltage, low battery voltage or missing/damaged battery
SYSTEM FAULT
(Yellow) Illuminated when the FACP is unable to provide mandatory
functions. Indicator is latched, until cleared by reset
EARTH FAULT
(Yellow) Illuminated when there is an earth fault detected on the panel
EXTERNAL BELL
FAULT
(Yellow) Illuminated if the External Bell output is in fault
FAULT
WARNING SYSTEM
(Yellow) Illuminated is the Warning System output is in fault
FAULT / ISOLATED
ACF
(Yellow) Illuminated steady if the ACF output has been disabled and flashes
if the ACF output is in fault (open or short circuit). Isolate has priority over fault
ASE FAULT
(Yellow) Illuminated when the ASE output is in fault
TEST
(Yellow) Illuminated when the FACP is in the test mode. Possible tests are
alarm, fault, walk, lamp and loop.
AIF ACTIVE
(Yellow) Illuminated when the AIF facility is active at the FACP
PRE ALARM
(Red) Illuminated when one or more devices are in the pre-alarm condition
and not disabled
DAY / NIGHT ACTIVE
(Yellow) Illuminated when day / night facility has been enabled on the FACP
(Yellow) Programmable 1 to 4 – For future use