Page 77
FIREFINDER SERIES II INSTALLATION, COMMISSIONING &
OPERATION
ALARM
ACK
(Red) General fire alarm indicator. The LED will flash until all alarms
have been acknowledged. Once Acknowledged the LED will remain steady until all alarms have
been cleared by Reset.
Acknowledge
Acknowledges the alarm condition of the sensor or conventional zone that is currently displayed on
the LCD.
If the key is held down for 3 seconds a lamp test is initiated. The Lamp Test illuminates all indicators,
segments on the LCD and momentarily sounds the buzzer
Active at access level 1 and 2.
RESET
FAULT
(Yellow) Indicator is illuminated when there is one or more faults on the system. Faults
can be;
Devices – missing, out of calibration, wrong type, reporting an internal error
Loops – short circuit or open circuit
Monitored inputs and outputs on loop devices
Sounders – missing, wrong type or reporting an internal error
Modules within the panel – missing, wrong type or hardware error
Main and secondary supplies
Reset
Resets the acknowledged alarm condition of the sensor or conventional zone currently displayed on
the LCD
Active at access level 2 only.
ISOLATE
ISOLATED
(Yellow) Indicator is illuminated when one or more device/s or conventional zones are
isolated either at the SmartTerminal or the FACP.
Isolate
Isolates (or de-isolates) the sensor or conventional zone currently displayed on the LCD
Active at access level 2 only