Specifications
Page 76
FIREFINDER SERIES II INSTALLATION, COMMISSIONING &
OPERATION
Controls & Indicators
ISOLATE
EXTERNAL
BELL
(Yellow) Illuminated when the External Bell output has been isolated either at the
SmartTerminal or the FACP.
External Bell Isolate
Press to isolate the External Bell output (associated LED illuminated).
Press again to re-enable the output (associated LED extinguished).
Active at access level 2.
ISOLATE
WARNING
SYSTEM
(Yellow) Illuminated when the Warning System output has been isolated either at the
SmartTerminal or the FACP.
Warning System Isolate
Press to isolate the Warning System output (associated LED illuminated).
Press again to re-enable the output (associated LED extinguished).
Active at access level 2 only.
PREVIOUS
Primary Function
Press to display the previously displayed LCD screen
Secondary Function
Set SmartTerminal address – A – (minus) decrement number
Active at access level 1 and 2
NEXT
Primary Function
Press to display the next displayed LCD entry
Secondary Function
Set SmartTerminal address – A + (plus) increment number