Specifications
Page 62
FIREFINDER SERIES II INSTALLATION, COMMISSIONING &
OPERATION
Configuration – Jumper Settings
JP 1 (Continuous / Flashing)
JP 2 (Single / Dual Stage)
1-2 Continuous
LED's Permanently
ON
1-2 Single Stage
Full sign on for Stage
1&2
2-3 Flashing
(DEFAULT)
LED's flashing at
1.5Hz
2-3 Dual Stage
(DEFAULT)
Half sign on for Stage 1
Full sign on for Stage 2
JP 3 (Enable Buzzer)
JP 4 (Disable External Mute)
1-2 ENABLE BUZZER
(DEFAULT)
Buzzer activates for
both Stage 1 & 2
1-2 EXTERNAL MUTE
(DEFAULT)
Disable external mute
for internal Buzzer
JP 5 ( Enable External Evacuation Device )
[not used]
1-2 Enable External
Evacuation
External evacuation
device will activate
on Stage 1 & 2
DEVICE (DEFAULT)
with the tone
dependent on the
input polarity
INPUT
INPUT
LEVEL 2
LEVEL 1
COM +
- +
TONE 1
+ -
TONE 2
TERM 5
TERM
4
TERM
6
TERM
3
TERM
1
OUTPUT
LEVEL 2
LEVEL 1
COM +
OUTPUT
- +
TONE 1
+ -
TONE 2
BUZZER
MUTE
OUTPUT
EXTERNAL
SOUNDER
SINGLE LEVEL
DUAL LEVEL
ENABLE
SOUNDER
(NOT USED)
ENABLE
BUZZER
DISABLE
EXT-MUTE
TP14
GND
TP9
TP8
TP7
TP13
TP12
TP11
TP10
TP1
GND
+
FLASHING
CONTINUOUS
ROW NOT USED
JP2
JP1
JP3
JP5
JP4
WARNING SIGN PCB
JP"X"
1 2 3
JUMPER
NUMBERING
BUZZER
TERM
2
ROW NOT USED
ROW NOT USED
TO N/O MUTE SWITCH
WARNING SIGN TERMINATION BRD
2 WIRE INPUT FROM AGENT TERMINATION BOARD
BUZZER MUTE
TO NEXT WARNING SIGN IF USED
FIT 10K EOL TO LAST SIGN (MAX 6)
10K
VANTAGE
SOUNDER
(MAX 1)
UNSCREW THE 4 SLOTTED
SCREWS TO REMOVE PCB
IN
-
OUT
+
+
-
CO M+
ST G1
ST G2
TB1
TB3
TB2
BRD 42WTB2-A
CN1/2
NOT
USED
BACKPAN RETAINING
SCREWS IN EACH CORNER
Figure 83: Warning Sign PCB Layout and Cabling
TERM 4
- +
TONE 1
INPUT
WARNING
SIGN
( MAXIMUM
OF 6 IN
TOTAL )
10K
1. (-) EVAC
2. (-) EVAC
3. (-) ALERT
4. (-) ALERT
5. (+) POS
6. (+) POS
VANTAGE SOUNDER
( ORDER CODE 205-0062 )
10K
FIT 10K EOL TO LAST
SIGN ON CHAIN
AGENT TERMINATION BOARD
RELEASE
-
+
STAGE2
+
-
N/0
COM
N/0
COM
+
SYST.
+ -
+ -
STAGE1
-
TB7
TB6
TB5
TB4
MAIN RESV
+ - Outputs are Monitored
INOP
+ -
TONE 2
TO NEXT WARNING SIGN IF
MULTIPLE SIGNS ARE USED
BRD 42WTB1-A
IN
-
OUT
+
+
-
COM+
STG1
STG2
TB1
TB3
TB2
NOTE: THE WARNING SIGN
TERMINATION BRD IS MOUNTED
ON THE INSIDE BACK PLATE
OF THE WARNING SIGN
BRD 42WTB2-A
CN1
CN2
Figure 84: 2 Wire Cabling from the Agent Termination Board to the Warning Sign/s & Evacuation Device/s