Specifications

Page 39
FIREFINDER SERIES II INSTALLATION, COMMISSIONING &
OPERATION
10 Accessing a Loop, Sensor or Zone
LOOP OR SENSOR
From the default display, press LOOP
Enter the loop number you wish to interrogate then press SENSOR.
Press the button for the sensor number.
Press the TO button if you wish to access a range of sensors on the loop,
Press the DISPLAY button if you wish to display the status of a sensor,
Press the ISOLATE button if you wish to isolate a sensor then ACKNOWLEDGE
Press the DE-ISOLATE button to de-isolate a sensor.
LOOP
1
ABC
SENSOR
JKL
4
TUV
7
TO
DISPLAY
For Multiple Devices
ISOLATE
ACKNOWLEDGE
Figure 53: Steps for Isolating Single and / or Multiple Devices
ZONE
From the default display, press ZONE
Press the button for the zone number.
Press the TO button if you wish to access a range of zones,
Press the DISPLAY button if you wish to display the status of a zone,
Press the ISOLATE button if you wish to isolate a zone then ACKNOWLEDGE
Press the DE-ISOLATE button to de-isolate a sensor.