Specifications

Page 52
FIREFINDER PLUS
(
AUST
)
INSTALLATION
,
COMMISSIONING OPERATION
8.9.8 Extra Devices Detected
The FireFinder PLUS LCD will indicate extra devices have been detected by displaying the screen
below and the FAULT LED will be illuminated.
FIREFINDER 26/2/2007 08:05:45
EXTRA DEVICES DETECTED
GOTO PROGRAMMING MENU TO RESOLVE
SYSTEM IS NOT NORMAL
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Figure 73: Resolving Extra Modules and Devices
To resolve select FUNCTION, enter PASSWORD, press
and the screen below will appear
PROGRAMMING MENU
0: RESOLVE EXTRA MODULES AND DEVICES
1: ON SITE PROGRAMMING
SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Figure 74: Added Module or Device
Select
(Selecting presents the PROGRAMMING MENU) then or (as seen below) then
ENTER to ADD the module or device to the configuration, or skip to resolve the changes manually in
the Programming Menu.
0: ADD EXTRA MODULES 1: ADD EXTRA DEVICES
2: DEVICE TYPE MISMATCH 3: MODE MISMATCH
SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Figure 75: Resolving Extra Modules or Devices
8.9.9 Mismatch Detected
If a mismatch is detected the Normal Default Screen will change to that shown below. Go to the
Programming Menu and select either
Resolve Extra Modules and Devices then
(Device Type) or
(Mode) to resolve the mismatch, OR On Site Programming to resolve manually.
Loop 1 Sensor 1
L1 S6 Z1 STAT: TYPE MISMATCH
ZONE FAULTS 1 of 1
Figure 76: Resolving a Mismatch