8.6 I/O
Press To display the Manual I/O Control menu
MANUAL I/O CONTROL
0: INPUT 1 :OUTPUT
2: REMOVE ALL MANUAL CONTROL
SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Figure 59: The Manual I/O Control Menu
Manual I/O control allows the technician to turn ON or OFF inputs and outputs off a device to facilitate
testing or isolation of plant during maintenance. Removal of manual control returns control to the
panel.
Press
Input Selected:
MANUAL INPUT CONTROL
0:IN A PANEL 1 :ON A LOOP
2:IN LOCAL BRIGADE CARD
3:REMOVE ALL MANUAL INPUT CONTROL
SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Figure 60: The Manual Input Control Menu
Press
IN A PANEL: Enter the I/O Controller number then the input number. This will display the
description for the input and its current state, you can then turn the input ON or OFF or remove
manual control.
ON A LOOP: Enter the loop number, the device number and the input number. This will display
the description for the input and its current state, you can then turn the input ON or OFF or remove
manual control.
IN LOCAL BRIGADE CARD: Will bring up the list and status of the Brigade card Inputs. These
can then be manually turned on and off with the exception off the MCP configured input
BRIGADE INPUT CONTROL
INPUT 1: (MCP ) OFF /NORM
INPUT 2: (EVACUATE) OFF /NORM
INPUT 3: (EXTERNAL FLT) OFF /NORM
INPUT 4: (RESET ) OFF /NORM
SELECT INPUT NO. TO CHANGE STATE
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0
Figure 61: Brigade Input Controls
Remove All Manual Input Control: Will remove all manual input control.
Output Selected: Same sequences as above for inputs but substitute outputs for inputs.
Remove All Manual Control Selected: Globally removes all manual control.