F eFiind Fire der PLLUS S Fire Alarm A m Con ntrol Pane el (A AS724 40 – 2 & 4 / AS4 4428 - 3) Ins stallattion, Com mmiss sionin ng & perattion Op MA AN299 94-2
RIGADE RE ESPONSE G FIRE BRIGADE B FIRE BR RESPONS R SE GUIDEGUIDE Resp ponding g to a Fire Acce ess Level 1 The indicator i willl be illumin nated. The applicable a zzone indica ator will also be illuminatted if a Zone e Board is ins stalled otherw wise details of the Loop, Sensor and d Zone es in alarm arre displayed on the LCD as follows. FIRST ALARM: A L1 D D1 Z1 15:31 D.DSC: :Loop 1 Sen nsor 1 Z.DCS: :Zone 1 LAST AL LARM: L4 D4 49 Z5 15:31 D.DSC: :Loop 4 Sen nsor 49 Z.
FIRE BRIGADE RESPONSE FIRE BRIGADE RESPONSE GUIDEGUIDE Disabling a Zone / Device Access Level 2 The following methods can be used to DISABLE a ZONE or Device: For Zones: Press then Press for Zone 1 selection. FIREFINDER 17/10/2013 09:00:00 ZONE:1 SELECT ZONE NO. THEN TO OR DISPLAY OR ZONE/DEVICE DISABLE/ENABLE KEY AC:2Z ALM:0 Now Press the PALM:0 FLT:0 DIS:0 . For Devices: Press the then enter Loop number, Press FIREFINDER LOOP:1 then enter device number.
TABLE OF CONTENTS Section 1 2 3 4 5 6 7 Page No. About This Manual ............................................................................................................ 1 1.1 Introduction .......................................................................................................... 1 1.2 General Requirements......................................................................................... 1 1.3 References ......................................................................
8 9 10 11 12 Tools .................................................................................................................. 39 7.8 7.9 Setup.................................................................................................................. 40 7.10 About.................................................................................................................. 41 The Function Menu ................................................................................................
13 14 15 16 17 18 19 20 21 22 23 24 12.15.5 Interface Wiring .................................................................................. 84 12.15.6 Warning Signs .................................................................................... 85 12.16 Occupant Warning Systems .............................................................................. 89 12.16.1 Amplifier Board (25W and 50W) ........................................................ 89 12.16.
FIREFINDER PLUS S (AUST) INSTALLA ATION,COMM MISSIONING G OPERATIO ON 1 Abou ut This Manual M 1.1 Introduction This manual conttains all the information required to install, comm mission and operate the e FireFinderr PLUS S Fire Alarm Control Pan nel (FACP) a and is only av vailable to and for the usse of personnel engaged d in its installation, commissioniing and operration. 1.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 2 Introduction 2.1 System Overview The purpose of the FireFinder PLUS Fire Alarm Control Panel (FACP) is to monitor changes in inputs, report those changes and update selected outputs as programmed. 2.2 Key Features The FireFinder PLUS panel is capable of supporting: Apollo Discovery and XP95 Intelligent Detectors, Multisensor, Photoelectric, Ionisation, Thermal (heat) and CO detectors.
FIREFINDER PLUS (AUST) 2.3 INSTALLATION,COMMISSIONING OPERATION Compliance The FireFinder PLUS FACP is approved to AS7240 – 2 & 4 and AS4428 – 3:2010 and includes the following ‘Optional requirements’ as defined by AS7240-2:2004: 7.8 Output to fire alarm devices 7.9.1 Output to fire alarm routing equipment 7.9.2 Input from fire alarm routing equipment 7.10.1 Output type A to fire protection equipment 7.11.1 Delays to outputs – configuration of delays (for item C) 7.11.
FIREFINDER PLUS (AUST) 2.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 3 FireFinder PLUS Description The following description does not relate to specific cabinets as the size of each cabinet will vary with the amount of hardware fitted. The heart of the FireFinder PLUS consists of two boards collectively known as the Controller. These boards are the Main Board and the CPU Board. Combining these two boards with a front panel forms the basis for a FireFinder PLUS FACP.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION FireFinder PLUS has an internal RS485 communication bus that allows for various ancillary boards (add on modules) to be connect to the panel. These boards can be used to control and monitor field plant equipment or the addition of an agent release module.
FIREFINDER PLUS S (AUST) INSTALLA ATION,COMM MISSIONING G OPERATIO ON 4 Placing The Basic Syystem Into Operaation 4.1 Unpac cking Careffully unpack the FireFind der PLUS. The p package sho ould include: FireF Finder PLUS S Fire Alarm Control Pan nel A CD D containing this “Installa ation and Com mmissioning” manual 003 keys 4.
FIREFINDER PLUS (AUST) 4.5 INSTALLATION,COMMISSIONING OPERATION Cabling Recommendations Conventional Zones Cabled in red Twin Plastic Sheath (TPS), Fire rated Radox or approved equivalent. Analogue Loop Two core cable. The minimum cable size is 0.75mm2, the maximum loop resistance is 50 ohms and the maximum loop distance is 2km. RS 485 Network Single twisted pair screened (2 core) cable originating from FACP extending through the protected areas and returning to the FACP.
FIREFINDER PLUS S (AUST) INSTALLA ATION,COMM MISSIONING G OPERATIO ON Co ommon Pow wer Supply Features F &S Specificatio ons Sw witch Mode Design D Over voltage e protection Hig gh efficiencyy, low working temp. High efficien ncy; low ripplle noise Un niversal AC input/ full ran nge Soft start with limiting AC C surge current Sh hort circuit/ over load Remote con ntrol on/off (ooption) Bu uilt in EMI Filter and PFC Circuit Over temp.
FIREFINDER PLUS (AUST) 4.6 INSTALLATION,COMMISSIONING OPERATION Power Supplies and AC Mains Installation Generally the AC Mains will be connected to either a 5 Amp, 14Amp or 22 Amp 27 volt supply. These supplies will be either mounted in the upper or lower right hand corner of the cabinet with the Brigade Board mounted in close proximity. The wiring should enter the cabinet through the nearest knockout entry hole on that side. Refer to Figures 6 - on for the wiring and fusing details for each supply.
FIREFINDER PLUS (AUST) 4.7 INSTALLATION,COMMISSIONING OPERATION CORRECT Power Up / Turn “ON” Procedure Once all the field devices are installed and the wiring has been correctly terminated the FireFinder PLUS is ready to turn on. For reliable power up it is essential the following procedure be followed; 4.8 1. Turn the Mains power on, THEN 2. Connect the batteries observing correct polarity. 3. The green power on LED should be illuminated.
JTAG CN2 U6 D9 C34 EOL D10 C35 CN11 COMMS. CN10 C58 C56 N1236 M16 CN10 RS485 COMMS. IN ZD5 1- To CN20 of the Main Controller Board 22/09/09 TB8 TB7 U7 BRD86BPSC4- 2 + 2- 3 + 34+ MONITORED OUTPUTS D11 C36 1+ U5 RL5 M15 RL4 M7 RL3 Q5 R108 RL2 L7 L8 TH8 CN6 RL1 M11 D7 CN5 E. BOARD CONTROL BAT- BAT+ 0 V +27V TB10 SGD E. BOARD SW.
FIREFINDER PLUS (AUST) 4.8.1 INSTALLATION,COMMISSIONING OPERATION Battery Connections A FireFinder PLUS requires two (2) 12 volt batteries (TB9). The batteries should be placed into the bottom right hand side of the cabinet. A red and black lead coming from TB1 on the Brigade Board will be clearly seen in the same area, this lead is to be connected to the batteries red to positive and black to negative once the system is operating on Mains supply.
FIREFINDER PLUS (AUST) 4.8.3 INSTALLATION,COMMISSIONING OPERATION Monitored Inputs Four independently monitored inputs (TB8) are provided and can be configured for a variety of uses. Manual Call Point (MCP) – if activated the FACP will go into alarm. Connected to the MCP on the front of the FACP. Class Change – if activated all Alarm Devices/Sounders and Alarm Device/Sounder Outputs in Sounder Group 1 are turned on.
FIREFINDER PLUS (AUST) 4.8.4 INSTALLATION,COMMISSIONING OPERATION Monitored Outputs Four independently monitored and controlled outputs (TB7) are provided and can be configured for a variety of uses. Alarm Devices - activated when any of its four sounder groups is active. (AS7240.2 Clause 7.7 and 7.8). The output is turned off during an Alarm (sounder) disable or Alarm (sounder) silence condition. ASE – (Australia Firefinder Plus Only) Fire/FARE – activated by alarm condition (AS7240.2 Clause 7.
FIREFINDER PLUS (AUST) 4.8.5 INSTALLATION,COMMISSIONING OPERATION Relay Output Connections Five “voltage free” relay outputs (TB2 – TB6) are provided and can be configured for a variety of uses. Alarm - activated on device alarm conditions and “Function” programmed logics. The relay is turned off during a ALARM disable condition. Sprinkler - activated on device alarm conditions and “Function” programmed logics.
FIREFINDER PLUS (AUST) 4.9 INSTALLATION,COMMISSIONING OPERATION Main Board The Main Board (BRD86MBA) carries the devices for interconnecting to all the other Boards, a buzzer for auditory indication, the backlight power supply for the LCD and CPU Reset. The Main CPU is mounted on this board and connected to it by CN11.
FIREFINDER PLUS (AUST) 4.10 INSTALLATION,COMMISSIONING OPERATION Front Panel Board The Front Panel Board (BRD86FPB) provides the buttons used to control the FACP as well as all LED indications. All LED’s are surface mounted and the buttons are embedded within the board. The LCD is viewed / protected by a clear Perspex screen.
FIREFINDER PLUS (AUST) 4.11 INSTALLATION,COMMISSIONING OPERATION Main CPU The Main CPU (BRD86MCPU) holds the main central processing unit including the Application software and Configuration settings for the FACP. The Main CPU is a 4-layer surface mount board The processor runs at 60MHz.
FIREFINDER PLUS (AUST) 4.12 INSTALLATION,COMMISSIONING OPERATION Slave CPU The Slave CPU (BRD86SCPU) provides the interfacing signals and I/O’s required to allow the FACP to connect / communicate to a variety of termination boards. A single chip micro controller U7 controls all operations of the FACP Slave CPU. This device contains the control program within Read Only Memory (ROM).
FIREFINDER PLUS (AUST) 4.13 INSTALLATION,COMMISSIONING OPERATION Addressable Dual Loop Termination Board The Addressable Dual Loop Termination Board (BRD86DLTB) acts as the interface between the external addressable devices and the control and monitoring functions of the FireFinder PLUS. Each board provides terminations for two loops and can be used with the Apollo range of detectors. One slave CPU is required per loop.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 4.13.1 Detector loop Isolator Installation In applications where it is not necessary to use an isolating base for each detector, up to 20 detectors may be installed between isolating bases. Note: Refer to Apollo Isolating specifications and guidelines for further details. If a short circuit or abnormally low impedance occurs, the base isolates the negative supply in the direction of the fault.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 5 FireFinder PLUS Control Panel #1 Figure 19: The FireFinder PLUS Control Panel The LCD is used to display abnormal conditions and for interrogation, control and programming activities. When the FACP is in its normal state a default screen is displayed. In access level 2 or higher the backlight shall always be ON. Alarm, Fault and Disable information is accessed through the Main Menu. #1 Is the intended area for the Alarm Routing Address Code.
FIREFINDER PLUS S (AUST) INSTALLA ATION,COMM MISSIONING G OPERATIO ON - Acctive at acces ss level 1, 2 and 3 Previous and Nexxt controls arre used to sccroll events on o the LCD. The T events bbeing display yed dependss on the current sellected view. When n the “SEVE ERAL ALARM MS” indicato r is illuminatted, then mu ultiple fire alaarms are pre esent on the e FACP P. In order to o view the ala arms the PR EVIOUS and d NEXT conttrols are usedd.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION - Active at access level 2 and 3 This control is used to disable (and enable) the Alarm Devices. If the indicator is “ON” Steady when any Alarm Devices (including Outputs configured as Alarm Devices) are disabled and flashes if Alarm devices are in fault. Disable has priority over fault. - Active at access level 2 and 3 This control is used to disable (and enable) all the ancillary outputs.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION After selecting the Loop number press this button to enter the device number for the device to be interrogated. Press this button followed by a number e.g. ZONE 4 to select the required zone. - Active at access level 2 and 3. Press this button after selecting the Zone number or the Loop and Device numbers to display the state of the device.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION - Active at access level 2 and 3 Used to cancel data into the current field. 10 consecutive entry of this key exits the current access level to the default access level. For example, if the current access level is “2”, 10 consecutive entry of this key will set the current access level to “1”. - Active at access level 2 and 3 Pressing the MENU button will display the main menu on the LCD.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION - This LED will be illuminated when there is a fault associated with the main or secondary power supply the following conditions constitute a fault. Faults are: Charger failure Battery voltage low Battery missing HCI missing PSU overload - The indicator is illuminated when there is a main system CPU fault present in the FACP. The indicator is latching and is cleared by activating the RESET control.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION - When this indicator is lit, the FACP is in the fault condition. The fault condition is non latching. Sources of faults are: Loop devices – missing, type mismatch, out of calibration / out of maintenance range, extra (or unexpected device), device related faults (esp.
FIREFINDER PLUS S (AUST) INSTALLA ATION,COMM MISSIONING G OPERATIO ON 6 Funcctions An nd Menu us IIMPORTANTT NOTE: It is stronglyy recommennded that all field proggramming changes c be e properly recorde ed. 6.1 The Default LCD D Display In its normal state e the FireFin nder PLUS w will display a screen similar to that shoown below.
FIREFINDER PLUS (AUST) 6.4 INSTALLATION,COMMISSIONING OPERATION Function Menu and Access Levels Three levels of ACCESS are available via separate passwords so that access to certain facilities can be restricted (such as the ability to enter new passwords). 6.4.1 Level I: Allows access to indications and controls to investigate and respond to a fire or fault warning. Level II: In addition to the level I facilities, quiescent, fire alarm fault warning, disable and test conditions.
FIREFINDER PLUS S (AUST) INSTALLA ATION,COMM MISSIONING G OPERATIO ON 7 The Main Meenu The M MAIN MENU U is accessed d by pressing g MAIN MENU U Numberin ng System: denotees the menuu structure number denotees the sub-m menu numb bering denotes a sub--menu within a sub- 0:ALARMS 1:STAGE 1 ALARMS 2:PRE-ALARM 2 MS 3:FAULTS 4:DISABLE ES 5:WALK 5 TEST TS 6:STATUS 7:TOOLS 8:SETUP 8 9:ABOUT SELECT NO O.
FIREFINDER PLUS S (AUST) 7.3 INSTALLA ATION,COMM MISSIONING G OPERATIO ON Pre-Allarms Presssing Disp plays all Pre--Alarms on th he system ZONE: 1 Zone 1 STATUS: : PRE-ALARM RM ‘DATE’ ‘TIME’ ZONE PR RE-ALARM AC:2Z ALM:0 1 OF 1 PALM:0 FLT:0 DEVICE> DIS:0 Figure 24 4: The PRE-A ALARMS dis splay Presssing the will dis splay the Devvice Informa ation the scre een, pressingg the it to Z Zone Informa ation 7.
FIREFINDER PLUS S (AUST) 7.5 INSTALLA ATION,COMM MISSIONING G OPERATIO ON Disablles Presssing Disp plays all Disa ables on the system. ZONE: 1 Zone 1 STATUS: : DISABLE ‘DATE’ ‘TIME’ ZONE DI ISABLE AC:2Z 1 ALM:0 OF 1 PALM:0 FLT:0 DEV VICE> DIS:0 Figure 2 28: The DISA ABLES displlay Presssing the will dis splay the Devvice Informa ation the scre een, pressingg the it to Z Zone Informa ation will return n NNote: If therre are no disables, a messsage, e.g.
FIREFINDER PLUS (AUST) 7.7 INSTALLATION,COMMISSIONING OPERATION Status Pressing Displays the Status of the system STATUS MENU 0:LOOPS 3:BRIGADE 6:ADD ONS 1:MODULES 4:SYSTEM SELECT NO. AC:2Z ALM:0 PALM:0 2:I/O 5:AVALUES FLT:0 DIS:0 Figure 31: The Status Menu (No networking) STATUS MENU 0:LOOPS 3:BRIGADE 6:AVALUES 1:MODULES 4:NETWORK 7:ADD ONS SELECT NO.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION DISPLAY INPUT/OUTPUT STATUS 0:OUTPUTS 1:INPUTS SELECT NO. AC:2Z ALM:0 PALM:0 FLT:0 DIS:0 Figure 35: The Display I/O Status display DISPLAY OUTPUT STATUS 0:IN A PANEL SELECT NO. AC:2Z ALM:0 1:ON A LOOP PALM:0 FLT:0 DIS:0 Figure 36: The Display Output Status display Once entered the LCD will then display a description of what that input or output does and its current state.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION Network Points: DISPLAY NETWORK POINTS 0:STATUS 1:POWER SUPPLY 2:BRIGADE SELECT NO. AC:2Z ALM:0 PALM:0 FLT:0 DIS:0 Figure 39: Display Network Points Network Points Screens are STATUS: Press, Select network point e.g.
FIREFINDER PLUS (AUST) / INSTALLATION,COMMISSIONING OPERATION ADD-ONS: Is pressed to access MODULE status DISPLAY ADD-ON MODULE STATUS NODE: 000 MODULE (1-32): SELECT ADD-ON MODULE NO.
FIREFINDER PLUS (AUST) 7.8 INSTALLATION,COMMISSIONING OPERATION Tools Pressing allows for the Testing of the following selected fields TOOLS MENU 0:ALARM 1:FAULT SELECT NO. AC:2Z ALM:0 PALM:0 2:LAMP FLT:0 DIS:0 Figure 44: The TOOLS menu Pressing brings up a further detailed selection sub-menu for an Alarm tests. ALARM TEST 0:ZONE 1:DEVICE SELECT NO.
FIREFINDER PLUS (AUST) 7.9 INSTALLATION,COMMISSIONING OPERATION Setup Pressing Displays the setup for sounders, Zone Delay and Printer SETUP MENU 0:SOUNDER 3:LANGUAGE 1:ZONE DELAY SELECT NO. AC:2Z ALM:0 PALM:0 2:PRINTER FLT:0 DIS:0 Figure 47: The SETUP menu Pressing brings up a further detailed selection sub-menu for Sounder O/P’s. SOUNDER MENU 0:SOUNDER ENABLE 1:SOUNDER DISABLE 2:SOUNDER RE-TRIGGER(ON) 3:SOUNDER RE-TRIGGER(OFF) CURRENT STATUS: ENABLE / RE-TRIGGER (ON) SELECT NO.
FIREFINDER PLUS (AUST) 7.10 INSTALLATION,COMMISSIONING OPERATION About Pressing Displays the panel’s application software version number and the title information. Title information could be company name, contact information and so on. ABOUT MENU VERSION#:1.01.00.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 8 The Function Menu The FUNCTION MENU is accessed by pressing button. A prompt will ask for a PASSWORD if the control panel is not currently active. Using the keypad key in the Level 2 or 3 PASSWORD. LEVEL III MAIN FUNCTIONS 0:DATE 1:TIME 4:TESTS 5:I/O 8:PROG 2:DAY/NIGHT 6:GLOBAL SELECT NO. AC:3Z ALM:0 PALM:0 3:LOGS 7:PASSWORD FLT:0 DIS:0 Figure 52: The Functions Menu (Level 3 screen shown) 8.
FIREFINDER PLUS S (AUST) 8.3 INSTALLA ATION,COMM MISSIONING G OPERATIO ON Day/Night Presss The DAY-NIGHT D SETTINGS screen will appear. Tim me entry is tthe same as s setting the e “Time e” facility. No ote this Functtion is availa able at Acces ss Level 3 on nly. Presss To ente er the DAY ON O time. Presss To ente er the NIGHT T ON time.
FIREFINDER PLUS (AUST) 8.5 INSTALLATION,COMMISSIONING OPERATION TESTS Press to access the TESTS menu. Note this is an Access Level 3 function only. TESTING MENU 0: WALK TEST 1:LOOP TEST 2: DEVICE LED TEST SELECT NO. AC:3Z ALM:0 PALM:0 FLT:0 DIS:0 Figure 57: The Testing Menu Press to initiate a WALK TEST: WALK TEST MENU 0: NEW ZONE WALK TEST 1: NEW ZONE SILENCE WALK TEST 2: VIEW ZONE WALK TEST SELECT NO.
FIREFINDER PLUS (AUST) 8.6 INSTALLATION,COMMISSIONING OPERATION I/O Press To display the Manual I/O Control menu MANUAL I/O CONTROL 0: INPUT 1 :OUTPUT 2: REMOVE ALL MANUAL CONTROL SELECT NO. AC:3Z ALM:0 PALM:0 FLT:0 DIS:0 Figure 59: The Manual I/O Control Menu Manual I/O control allows the technician to turn ON or OFF inputs and outputs off a device to facilitate testing or isolation of plant during maintenance. Removal of manual control returns control to the panel.
FIREFINDER PLUS (AUST) 8.7 INSTALLATION,COMMISSIONING OPERATION Global (Network Panels) Press To display the Global Output Control menu GLOBAL OUTPUT CONTROL 0:FWRE OUTPUT 1:FARE OUTPUT 2:WARNING SYSTEM OUTPUT SELECT NO. AC:3Z ALM:0 PALM:0 FLT:0 DIS:0 Figure 62: The Global Output Control Menu Press FWRE OUTPUT: Provides control to disable or enable the FWRE outputs. Press ENABLE DISABLE FARE OUTPUT: Provides control to disable or enable the FARE outputs.
FIREFINDER PLUS (AUST) 8.8 INSTALLATION,COMMISSIONING OPERATION Passwords (Level III) Press While in the Main Functions menu and enter the Level III Password if in Access Level II or, if in Access Level III to display the Password Menu. PASSWORD MENU 0: ADD PASSWORD 1 :DELETE PASSWORD 2: DELETE ALL PASSWORDS SELECT NO. AC:3Z ALM:0 PALM:0 FLT:0 DIS:0 Figure 63: The Password Menu Add Password: Enter the new password, then press number. .
FIREFINDER PLUS S (AUST) 8.9 INSTALLA ATION,COMM MISSIONING G OPERATIO ON Progra amming Presss To disp play the Leve el III Program mming Menu.. ON SITE E PROGRAMMI MING MENU 0: CONV V ZONE 1 :D DEVICE 2:INPUT 3: OUTPUT 4: PANE EL BASED MC MCP 5:SUB ADDRESS A 6:ZONE PROGRAMMIN NG SELECT NO. AC:3Z ALM:0 PALM:0 FLT:0 DIS:0 Figure e 64: Program mming Menu u 8.9.
FIREFINDER PLUS S (AUST) INSTALLA ATION,COMM MISSIONING G OPERATIO ON EDIT Z CONFIGURAT ATION CONFIG: : LATCHING G Use < or o > to cha ange alarm m setting AC:3Z ALM:0 PALM:0 FLT:0 DIS:0 Figurre 67: Zone C Configuration n Latching / Non-latching N g Use or to change c the ssetting Confiiguration setttings are Latching, Non--Latching, AV VF, Self Res set ( 0 to 999 seconds ). After setting g the C Configuration the ZONE I//O GROUPS S are program mmed.
FIREFINDER PLUS S (AUST) INSTALLA ATION,COMM MISSIONING G OPERATIO ON et / Edits and enables / disables the d ay/night setttings then. 4. Se Preess 5. Allocates / Editts the Loop and a Devices Groups. After scrolling through the groups g a pro ompt tells th he operator to press chang ges. 8.9.3 3 to confirm the e Input Presss INPUT: By following the screen s promp pts as above e Edit or Dele ete an INPUT T in a panel oor a loop.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION EDIT ZONE: 1 DESC STRING DESCR> TO EDIT NEXT FIELD] AC:3Z ALM:0 PALM:0 FLT:0 DIS:0 Figure 69: Zone Programming - Description Press the key to edit the next field (Day Night Settings).
FIREFINDER PLUS (AUST) 8.9.8 INSTALLATION,COMMISSIONING OPERATION Extra Devices Detected The FireFinder PLUS LCD will indicate extra devices have been detected by displaying the screen below and the FAULT LED will be illuminated.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION Self Learn is enabled / disabled in the EEPROM programming. If enabled FireFinder PLUS has the ability to detect extra or missing modules or devices, (that is devices or modules that have been added or removed) or there has been a change of the type of module or device. Note: If a change does occur the FACP will take 30seconds to register the event on the LCD and illuminate the FAULT LED.
FIREFINDER PLUS S (AUST) INSTALLA ATION,COMM MISSIONING G OPERATIO ON 9 Incom ming Firre Alarm Signal Will operate o the red r common n LED fire ind dicator Will display d locattion of fire ala arm origin on n the LCD Will activate a exte ernal alarm. Will activate a the internal FAC CP buzzer. Will activate a any ancillary equ uipment so programmed p . Will abort a any tes st in progresss.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 10 Accessing a Loop, Device or Zone LOOP OR DEVICE From the default display, press Enter the loop number you wish to interrogate then press Press the button for the device number. Press the button if you wish to access a range of devices on the loop, Press the button if you wish to display the status of a device, Press the button if you wish to disable a device Press the button to re-enable a device. .
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 11 Modem / Programming / Debug Interfacing The modem I/O port is a Dual DB9 connector (CN8 situated on the lower left hand corner of the Main Board BRD86MBA) that is normally used for programming of the FACP via the serial port of a PC or Laptop. There is also a USB connector (CN25) provided to allow programming of the FACP from a USB port of a PC.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 12 Expanding the FACP with Compatible FireFinder PLUS Boards 12.1 Ancillary Services The FACP has been designed such that detectors and/or call points, in addition to giving an alarm and calling the fire brigade, will close or open circuits of ancillary services by means of relays or similar devices.
FIREFINDER PLUS (AUST) 12.3 INSTALLATION,COMMISSIONING OPERATION Expansion Board The Expansion Connection Board (BRD86FEPB) is used to increase the capacity of the controller from 4 Slave CPU’s to 8 allowing Loops 5 – 8 to be configured. Connection from the Controller to the Expansion Board, which must be mounted within 200mm of the Controller, is made via a 20 way flat cable Slave CPU number 5 is an integral part of the Expansion Board, only Slave CPU’s 6 (CN2), 7 (CN3 and 8 (CN4)are plug ins.
FIREFINDER PLUS (AUST) 12.4 INSTALLATION,COMMISSIONING OPERATION 8 Zone Conventional Board This board (BRD43EZC) has 8 conventional zones. Up to 999 zones max may be configured. The zones may be used in panel programming and Input / Output programming.
FIREFINDER PLUS (AUST) 12.5 INSTALLATION,COMMISSIONING OPERATION 32 Zone Alarm Mimic Card Each card (BRD43ZAMC) has 32 bi-coloured LED’s which can be used to display the status of up to 32 Zones.
FIREFINDER PLUS (AUST) 12.6 INSTALLATION,COMMISSIONING OPERATION 8 Way Switch and Indicator Card This card (BRD25GIB-B) has 8 switch inputs and 8 LED indicator outputs. The switch inputs and LED outputs may be used in Input Output programming. The switches are configurable as either momentary or toggle switches. When configured as momentary pressing the button once will cause an event to occur as programmed in I/O and the LED’s can be programmed to operate as an output.
FIREFINDER PLUS (AUST) 12.7 INSTALLATION,COMMISSIONING OPERATION 16 Way Input Board The 16 Way Input Board (BRD25SIP) makes provision for 16 voltage free contacts to be terminated to 16 optically coupled inputs. Its application is primarily for the monitoring of controlled ancillary equipment or to initiate an action / event due to a change of state from what is accepted as the norm. Note: These inputs are not monitored for faults.
FIREFINDER PLUS (AUST) 12.8 INSTALLATION,COMMISSIONING OPERATION 8 Way Relay Board The Relay Board (BRD25EWRB) provides 8 programmable relays with 30VDC 1 Amp voltage free change over contacts for control or monitoring purposes and comes fitted for internal or external FACP use. The functionality and programming of the relays is similar to the relays on the main board of the FACP. By default the relays default to Common Alarm functionality. All terminal points are protected.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 12.8.2 Remote Relay Board In the remote version the Comms In and Out Terminal Block TB9 is cabled to the RS485 Comms terminal block TB1on the Communications Extender Board (see section 5.12) and can be installed up to 1.2kms from the FACP. Note: Can be powered from the panel or an external 27 volt source.
FIREFINDER PLUS (AUST) 12.9 INSTALLATION,COMMISSIONING OPERATION 8 Way Sounder Board The Sounder Board (BRD25SOP) expands the number of sounders that can be used on an FACP by 8. Each output is of a solid state design, rated at 24VDC / 750mA and requires a 10KΩ End of Line (EOL) resistor regardless of whether or not a sounder is wired to the circuit.
FIREFINDER PLUS (AUST) 12.10 INSTALLATION,COMMISSIONING OPERATION 4 Way Fire Fan Module The Fire Fan Module (BRD25FCB) has four (4) separate fan controls each having an On, Auto and Off function switch and a set of three (3) monitoring LED’s. The LED’s indicate the status of the equipment e.g. Run, Fault or Stop. The two (2) arrow head buttons are used to step up and / or down through the three (3) conditions. A slip in label can also be inserted into the hinged cover for identification purposes.
FIREFINDER PLUS (AUST) 12.11 INSTALLATION,COMMISSIONING OPERATION 4 Way Fan Termination Board The Fan Termination Board (BRD25FTB) interfaces between the Fire Fan Module and the plant/equipment it controls via the 24 volt 250mA Start, Stop, current limited, relay outputs and monitor inputs. Programmable monitoring of the field equipment is achieved using 0 volts as an input level to indicate run, fault and stop conditions of that equipment.
FIREFINDER PLUS (AUST) 12.12 INSTALLATION,COMMISSIONING OPERATION Bargraph Display Card The Bargraph display card (BDC) provides a smoke obscuration bargraph, alarm indicators, a reset and disable facility for a Pro-Sens fitted with an Ampac version of an APID fitted. The BDC supports two detectors, which can be located in the same Pro-Sens unit or separate ProSens units. 12.12.
FIREFINDER PLUS (AUST) 12.13 INSTALLATION,COMMISSIONING OPERATION Communications Extender Board The Communications Extender Board (BRD82LTB-C) is mounted inside the FACP and provides protected RS485 communications and 27VDC to the SmartTerminal and other external modules.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 12.14.2 Mechanical SmartTerminal is supplied in an ABS cabinet and consists of; The Main Card, with all controls and indicators mounted directly onto it 1 X Termination Board 2 X ABS door keys 2 X 003 Enable / Disable keys 2 X Jumper links 2A Power Supply ( only if internally powered ) Note: A Communications Extender Board will be required if the Comms Bus in the FACP is fully utilised and / or if one is not fitted.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 12.14.3 Installation & Cabling SmartTerminal is connected to the FACP as shown below.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 12.14.5 Operation The operation of SmartTerminal can be considered to be in one of three states, these are; 1. Power up - when the SmartTerminal is initialising 2. Normal - when the SmartTerminal address has been set and is communicating with the FACP, reporting normal / abnormal conditions and controlling the FACP via the front panel controls 3. Fault where the SmartTerminal is in fault and/or is unable to communicate with the FACP.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 12.14.6 SmartTerminal Controls and Indicators All controls, except for the controls Enable / Disable Keyswitch, are of a momentary push button style and operate in exactly the same way as does the FACP itself. Figure 99: SmartTerminal Front Panel Layout 12.14.7 SmartTerminal Screen Format There are 3 events that can be reported and displayed by SmartTerminal. The types of event are; Fire Faults and Disables.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION Fault: If configured the screen format for reporting loop / device / zone fault condition is: Zzzz
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION Normal / Default: The format for reporting that everything is normal is:
FIREFINDER PLUS (AUST) 12.15 INSTALLATION,COMMISSIONING OPERATION Agent Release Control Agent Release control consists of an Agent Release Module, Termination Board and an optional Local Control Station. 12.15.1 Operation Introduction The Agent Release Module and Termination Board communicate with the FACP via the RS485 multidrop bus. The Local Control Station communicates only with the Termination Board via a separate RS485 bus. Up to 4 Local Control Stations can be connected to one termination board.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION Note: A “manual release” can still be initiated in “auto mode” but the LCS “Inhibit” control WILL NOT inhibit / abort the agent release sequence. Single Zone Activation, the following discharge sequence is executed; Automatic Activation LED is illuminated on the Agent Release Module and Local Control Station. Stage 1 outputs are switched to +24VDC. (FIRE ALARM sign illuminated, aural alarm sounds). Stage 2 outputs are switched to +24VDC.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION Note #1: The common fault indicator on the Agent Release Module and Local Control Station is illuminated for any Fault condition. Note #2: For a pressure switch fault, low pressure switch fault, lock-off valve fault, stage 1 output fault, stage 2 output fault and interlock fault, the FACP will signal the brigade.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 12.15.2 Agent Release Module The Agent Release Module controls and monitors all the requirements for agent release.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 12.15.3 Local Control Station The Local Control Station is supplied fitted into an IP40 rated enclosure and has the same indicators and Manual Release switch as the Agent Release Module within the Fire Alarm Control Panel (FACP) but no Agent Select button or Service Inhibit keyswitch. The Comms line is RS485 and is cabled to the Agent Termination Board. The Interlock is a monitored input with 10KΩ EOL.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION Agent Release / LCS Indicators There are 12 indicators on both the Agent Release Module and Local Control Station. They are; MANUAL ACTIVATION (Red) Illuminated when a manual release sequence has commenced. A Manual release sequence can only be started by activating the manual release at the FACP or LCS. The indicator is extinguished by activating RESET on the FACP.
FIREFINDER PLUS (AUST) RESERVE AGENT INSTALLATION,COMMISSIONING OPERATION (Yellow) Illuminated when the “Reserve Agent” is selected. Local Control Panel Inhibit The agent inhibit switch has an internal lamp fitted with yellow lens. Illuminated when the inhibit switch is activated at the FACP or any of the LCS’s. Buzzer (located at the FACP) The Buzzer sounds; Under all fault conditions and can be silenced by using the appropriate FACP buzzer silence control.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION SIG+ 0VDC SCRN SIG+24VDC GAS SYST. 10K 10K INPUTS LCS CABLE TB1 22K 22K 22K 12.15.4 Agent Release Termination Board + LOCK- + PSW - N/0 CO M TB3 TB2 MONITORED + - + TB4 - N/0 C O M TB5 FIRED INOP C N 1 RS485 Control Comms In C N 2 RS485 Control Fit EOL Termination Comms Out CN3 CN4 ON 1 2 3 4 STAGE2 STAGE1 + L.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 12.15.5 Interface Wiring Monitored Inputs TB2 1 & 2 Solenoid & Metron This input relies on N/O or N/C relay contacts used in conjunction with 22K EOL and 4K7 series resistors. The type of agent release mechanism and contacts used has to be set in the Programming Menu for the input to function as per the manufacturers specifications and be in accordance with the relevant Standard.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 12.15.6 Warning Signs Introduction The Ampac Warning Signs provide clear, visual and audible indication of an alarm event and are designed for use with fire detection and alarm systems which may incorporate agent release capability. The display may also be customised as required to cater for a variety of applications.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION The weatherproof enclosure should be surface mounted using appropriate fixings and sealing washers. 1. Using the 6x outer screws, remove the clear Perspex lid. 2. Using the 4x black dome nuts, remove the text legend fascia plate bezel. 3. Remove the internal printed circuit board using the 2x screws located in the centre of the PCB. 4.
SW2 N1236 02/04/13 BRD42WSB1- 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 OFF D49 D45 DC+ D38 D32 D26 D21 ON TB1 ST1 D6 D2 LEVEL 2 ON FOR STAGE 1 INPUT LEVEL 1 OFF FOR STAGE 2 INPUT LEVEL 1 LEDs FLASHING LEVEL 2 LEDs FLASHING INTERNAL BUZZER ENABLED BUZZER PULSING EXTERNAL MUTE INPUT DISABLED SYNCHRONIZING OUTPUT ENABLED* INPUT FROM FIRE PANEL ST2 FOR FURTHER INFORMATION PLEASE REFER TO WWW.AMPAC.
SW2 N1236 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 OFF D49 D45 LEVEL 2 OFF FOR STAGE 1 INPUT LEVEL 1 ON FOR STAGE 2 INPUT LEVEL 1 LEDs CONSTANT LEVEL 2 LEDs CONSTANT INTERNAL BUZZER DISABLED BUZZER CONTINUOUS EXTERNAL MUTE INPUT ENABLED SYNCHRONIZING OUTPUT DISABLED LEVEL 2 LEVEL 1 SW. D37 D31 D25 D20 DC+ D26 ON TB1 ST1 FOR FURTHER INFORMATION PLEASE REFER TO WWW.AMPAC.
FIREFINDER PLUS (AUST) 12.16 INSTALLATION,COMMISSIONING OPERATION Occupant Warning Systems The OWS system is intended to broadcast information (voice announcements for emergency purposes, alert signals, evacuate signals, visual and tactile warning devices) to provide warning to the occupants within one or more specified areas in an emergency, to effect a rapid and orderly mobilisation of occupants in an indoor or outdoor area.
FIREFINDER PLUS (AUST) Relay 1 Relay 2 Relay 3 INSTALLATION,COMMISSIONING OPERATION Emergency: Relay Closed (energised) Quiescent: Relay Open (de-energised) No Power: Relay Open (de-energised) Disabled: Relay Closed (energised) Enabled: Relay Open (de-energised) No Power: Relay Open (de-energised) Fault: Relay Closed (energised) No Fault: Relay Open (de-energised) No Power: Relay Open (de-energised) Emergency Warning Condition Test Mode Fault Relay The Strobe Output functions as follows: Strobe Provi
FIREFINDER PLUS S (AUST) INSTALLA ATION,COMM MISSIONING G OPERATIO ON 12.16 6.
FIREFINDER PLUS (AUST) 12.17 INSTALLATION,COMMISSIONING OPERATION Printer Specifications Printing method: directed impact dot matrix Interface: 8 bit parallel interface Printing mechanism: 4/6 pin shuttle Interface port: 26 PIN flat plug 12.17.1 Indicators and Buttons The front panel has an LED indicator and two buttons SEL (SELECT), LF (LINE FEED).
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION Self-Test Mode With power applied (green LED illuminated) push the SEL button. This will turn off the LED. Press and hold in the LF button, then press the SEL button again and the printer will enter the Self Test mode. Self-test will print out all the valid characters in the character sets.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION Figure 117: Head Mechanism Rotation and Paper Roll Removal / Insertion 1. Take out the empty paper roll and roller 2. Put the new paper roll onto the paper roller and replace as shown above. 3. Connect to the power supply. 4. Press the SEL button to take the printer Off Line, (LED is off). 5. Press the LF button, (paper feed). 6. Feed the edge of the paper into the mechanism and allow it to feed through. 7.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 12.17.3 Printer Connections and Jumpering Mounted on the back of the printer mechanism is the PCB that carries the; Connectors for interconnection to the Main Board, Jumper links required to set the programmed print modes; and Printer 5 volt DC Power Supply.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 13 Expanding the System through Networking Expanding the system can be achieved in various ways and requires the use of boards specifically designed for communications purposes and boards that actually expand the system. 13.1 Networking When FACP’s are connected to each other they form a “NETWORK“. Individual FACP’s in the Network are referred to as NODES.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION PANEL 1 16 Way BACKLIGHT RESET SW 1 MAIN BOARD EXPANSION MODULE CN17 SLAVE 4 CN100 4 SLAVE 3 CN13 CN3 CN20 SLAVE 2 CN14 3 MAIN BOARD INTERFACE CN15 2 CN18 CN6 POWER SW2 SW1 CN10 TERMINATION BOARD CN26 27V IN COMMS OUT SHD + - CN7 TB2 SH D PSU MONITOR BRIGADE I/F LK1 + - EXPANSION MODULE SH D COMMS IN SHD + - + SHIELD LINK PRINTER RS485 COMMS IN RS485 C OMMS OUT C18 D6 ISOLATED + D1 D2 OFF SW2 SW3 CN
FIREFINDER PLUS (AUST) 13.3 INSTALLATION,COMMISSIONING OPERATION High Level Interface Expander Hardware The High Level Interface Expander (BRD43SPB) consists of a serial port under the control of a microcontroller. Communications between the FACP and this board is via the RS485 control bus with each board having a dedicated link and selectable 4 bit address. The Serial/Parallel Board consists of serial ports, a parallel port and an Ethernet port all under the control of a microcontroller.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION NODE 1 MAIN CONTROL BOARD TB1 CH16 RJ45 CN20 CN13 CN18 CN2 + RN20 - SLAVE CPU +2 7V RN17 CH8 CH8 CH6 CN5 FACP COMMS FACP EOL - + 0V 0V RS485 EOL HLI CONTROLLER ADDRESS LSB MSB - + TB3 CN8 D7 D6 1 ZDN2 1 2 3 4 RS 232 RS 485 RJ45 TB1 TP3 D14 CN10 PSU MONITOR BRIGADE I/F + + 16 Way +27 V TB2 + 27V CN5 P O W ER FACP E OL D12 LK3 - + CN8 D7 D6 ZDN2 CH16 + - COM RS485 OUT CN20 CN14 4 SW 1 CN2 CN
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 14 List of Compatible Devices Conventional Detectors The following range of conventional detectors has approval to be used with the FireFinder PLUS conventional zone board.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 15 Certification Information The FireFinder Plus is designed and manufactured by: AMPAC TECHNOLOGIES PTY LTD 7 Ledgar Rd Balcatta 6021 Western Australia PH: 61-8-9242 3333 FAX: 61-8-9242 3334 Manufactured to: Certificate of Compliance Number: Equipment Serial Number: Date of Manufacture: Page 101
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 16 Maintenance and Troubleshooting Chart 16.1 Maintenance The FireFinder PLUS FACP should be maintained so as to comply with all standards / regulations applicable to the country and location it has been installed. Failure to do so could put at risk compliance and the integrity of the system. As a minimum it is recommended the following be used as a guide to periodic maintenance especially if there is an absence of standards regulations.
FIREFINDER PLUS (AUST) 16.2 INSTALLATION,COMMISSIONING OPERATION Troubleshooting FireFinder PLUS Resolution of all suspected faults MUST only be carried out by suitably qualified technical operatives. Problem No Mains Power Power Fault LED illuminated Solution Check mains Fuse Check output voltage it should be set to 27.6V. Low = (less than 26.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 17 Compatible Devices AMPAC Type Code Auto Learn Default Displayed chars) Device Type Type (19 Type Desc Optical 05h XP95 Optical XP95 PHOTO PHOTO 05h XP95 Optical with base sounder XP95 PHOTO + SNDR PHOTO 05h XPander Optical XPANDER PHOTO PHOTO 05h S90 Optical S90 PHOTO PHOTO 05h Xplorer Optical XPLORER PHOTO PHOTO 05h Xplorer Optical with base sounder XPLR PHOTO + SNDR PHOTO 05h XP95 Beam XP95 BEAM PHOTO 0D
FIREFINDER PLUS (AUST) AMPAC Type Code Auto Learn Default INSTALLATION,COMMISSIONING OPERATION Displayed chars) Device Type Type (19 Type Desc Manual Call Points 07h S90 MCP S90 MCP MCP 11Fh Discovery MCP DISC MCP MCP 1Fh XP95 MCP XP95 MCP MCP 1Fh XPander MCP XPANDER MCP MCP 1Fh XP95 Mini switch monitor with interrupt XP95 MINI SW + INT MCP 1Fh Xplorer MCP XPLORER MCP MCP XP95 sounder / sounder control unit XP95 SOUNDER SNDR 01h XPander sounder XPANDER SOUNDER S
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 18 Address Setting BINARY ADDRESS SETTING (APOLLO) SERIES XP95 - ADDRESS DATA DIL SWITCH: ON = 1 OFF = 0 ADDRESS TAG FOR DETECTORS (I/O DEVICES) DIL switch setting DIL switch setting DIL switch setting DIL switch setting DIL switch setting Address 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 1234567 1000000 0100000 1100000 0010000 1010000 0110000 1110000 0001000 1001000 0101000 1101000 0011000 1011000 0111000 1111000 0000100
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 19 Glossary of Terms ACF: ANCILLARY CONTROL FACILITY ACKD: ACKNOWLEDGED AHU: AIR HANDLING UNIT ALM: ALARM AVF: ALARM VERIFICATION FACILITY AZF: ALARM ZONE FACILITY AZC: ALARM ZONE CIRCUIT C: RELAY COMMON CONTACT (WIPER) CIC: CONTROLLER INTERFACE CARD CN: CONNECTOR CPU: COMMON PROCESSOR UNIT DGP: DATA GATHERING POINT EARTH: BUILDING EARTH EOL: END OF LINE FACP: FIRE ALARM CONTROL PANEL FLT: FAULT GND: GROUND (0 VOL
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 20 Definitions Addressable system - a fire alarm and detection system that contains addressable alarm zone facilities or addressable control devices. Alarm Verification Facility (AVF) - that part of the FACP, which provides an automatic resetting function for spurious alarm signals so that they will not inadvertently initiate Master Alarm Facility (MAF), or ACF functions.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 21 Specifications Metal Only) SP1M (Europe Metal SP8X Mechanical Dimensions Cabinet: ( mm ) Material Environmental Temperature: Humidity: IP rating Mains Input Input Voltage: Protection (Quick Acting Fuse): 5 AMP Supply 18 AMP Supply Minimum Cable Requirements: Power Supply 505 (H) x 407 (W) x 150 (D) 1.2mm Mild Steel 845 (H) x 518.5 (W) x 173(D) Includes window outer door 1.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION Metal SP1X Metal SP16X 505 (H) x 407 (W) x 150 (D) Includes window outer door 1.2mm Mild Steel 1200 (H) x 625 (W) x 240 (D) Includes window outer door 1.
7 Page 111 FUNCTION ACCESS* FUNCTION MENU DATE ZONE ALARM TOOLS WALK TEST ALARMS 1 1 0 0 6 1 TIME DEVICE PRINT ALL DEVICES LOOPS STATUS STAGE-1 ALARM 0 2 DAY TIME DAY/NIGHT NIGHT TIME 1 * ENTER ACCESS CODE FOR LEVEL 3 FUNCTIONS 0 0 0 7 5 0 = ACCESS LEVEL 3 = ACCESS LEVEL 2 2 0 0 3 0 1 1 ENABLE / DISABLE PRINT ENTRY ALARM LOGS ZONE FAULT PRINT TOTAL PRE-ALARMS 2 SHOW OPTIONS FAULT DEVICE SLAVE MODULES ZONE / DEVICE FAULTS TESTS WALK TEST 0 4 VI
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION 23 Statement of Compliance Please PRINT 1. Name of Building: 2. Address: 3. I/We have installed in the above building an alteration to the system manufactured by, OR a system manufactured by. (Name of Service Provider) 4. The system is connected to monitoring service provider by a Permanent , Non-Permanent connection 5. Date of connection / / 6. Ancillary equipment installed / connected to the control and indicating equipment.
FIREFINDER PLUS (AUST) 15. INSTALLATION,COMMISSIONING OPERATION I/We 1. 2. 3. Print Name/s Hereby certify that the installation has been thoroughly tested from each actuating device and that a test of the transmission of the alarm signal to the monitoring service provider has been satisfactorily carried out. I/We further certify that the whole system and all components called up in Clause 1.3 in connection therewith are installed entirely in accordance with the current requirements of AS 1670.
FIREFINDER PLUS (AUST) 23.1 INSTALLATION,COMMISSIONING OPERATION Installation Details # Indicate with a number in brackets the number of actuating devices in concealed spaces. * Add addressable loop number in brackets where applicable.
FIREFINDER PLUS (AUST) 24 INSTALLATION,COMMISSIONING OPERATION Commissioning Test Report This FireFinder PLUS Fire Alarm Control Panel is installed at: Company Name Street Suburb State Country / Post Code (Company Name & Installation Address ) Owner or Owners' Authorized Representative: Company Name Street Suburb State Country / Post Code Type of Installation: (Circle) NEW MODIFIED Date of commissioning tests: Name and address of commissioning company, Company Name Street Suburb State Country /
FIREFINDER PLUS (AUST) 24.1 INSTALLATION,COMMISSIONING OPERATION Procedure The following tests are the minimum that shall be performed when commissioning a system using the FireFinder PLUS Fire Alarm Control Panel. Supplements to these tests may be added by way of attachments or notation (using waterproof ink) to this documentation. If supplements or tests are added reference to them shall be made at an appropriate point on this document.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION including that the receiver responds to signals from an actuating device for alarm, tamper, low standby power signals and gives a fault signal when the supervisory signal condition is absent. (j) Operation of fault and alarm signals: Fault and alarm conditions correctly detect and indicate as the correct. alarm zone, operating other required indicators, and operate relevant outputs of the CIE.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION (ii) There are no ‘blind’ spots in the area protected. (iii) Detectors are rigidly fixed. (iv) Detector lenses are clean and adequately protected from dust and extraneous radiation sources. (v) Detectors respond to a flame or simulated flame source.
FIREFINDER PLUS (AUST) INSTALLATION,COMMISSIONING OPERATION
FIREFINDER PLUS S (AUST) INSTALLA ATION,COMM MISSIONING G OPERATIO ON UNCO ONTROLLED D DOCUMEN NT NOTE: Due e to AMPAC’s commitment to ccontinuous impro ovement specifi fications may chhange without no otice.