Specifications
Page 68
EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION
No Communication
Device Isolate / Disables: If configured the screen format for reporting loop / device / zone disable
condition is:
<point location> DISABLED
<point descriptor> <type>
<date> <time>
FIRE XXX OF XXX
Pre-alarm: If configured the screen format for reporting loop / device / zone Pre-alarm condition is:
<point location> PRE-ALARM
<point descriptor> <type>
<date> <time>
PRE-ALARM XXX OF XXX
Normal / Default: The format for reporting that everything is normal is:
<DATE> <TIME>
<SYSTEM STATUS>
The default screen is only displayed when there are no device alarms, device faults or device
disables present on the system.
The highest priority current system status will be displayed and can be one of the following listed in
order of highest to lowest priority:
“SYSTEM ALARM”
“SYSTEM PRE-ALARM”
“SYSTEM FAULT”
“SYSTEM ISOLATE”
“SYSTEM NORMAL”
Config: The Config screen displays the following.
VX.X (software version number
Address
A- A+ C- C+
A - , A + : adjusts the address 1 to 30, 30 being the maximum number of SmartTerminal’s that can
be connected to the FACP, ( default is 255 which is not a valid address).
The function buttons perform the following;
A – Press “Previous” A+ press “Next”
C - C+: decreases [-] and increases [+] the LCD contrast level.
The function buttons perform the following;
C – Press “Silence Buzzer” C+ press “Reset”