Specifications

Page 67
EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION
12.13.6 SmartTerminal Controls and Indicators
All controls, except for the controls Enable / Disable Keyswitch, are of a momentary push button
style and operate in exactly the same way as does the FACP itself.
Figure 94: SmartTerminal Front Panel Layout
12.13.7 SmartTerminal Screen Format
There are 3 events that can be reported and displayed by SmartTerminal. The types of event are;
Fire
Faults and
Disables.
The types of events are only associated with devices and detectors hence faults associated with
modules, loops O/C S/C, power supplies and so forth are not reported on the LCD.
The SmartTerminal has front panel indicators for each type of event. When SmartTerminal is
configured not to report a type of event and that event type is present (and the corresponding front
panel indicator is illuminated on the SmartTerminal), then a standard information screen is
displayed on the LCD stating the system is not normal and the operator should see the FACP.
Alarm: If configured the screen format for reporting loop / device / zone fire condition is:
<point location> FIRE
<point descriptor> <type>
<date> <time>
FIRE XXX OF XXX
Fault: If configured the screen format for reporting loop / device / zone fault condition is:
<point location> FAULT
<point descriptor> <type>
<date> <time>
FIRE XXX OF XXX
Note: The fault types only relate to devices.
In the event of a loss of communications, for a period of greater than 15 seconds the SmartTerminal
will default to the No Communications screen. The format for this screen is: