Specifications
Page 55
EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION
12.5 32 Zone Alarm Mimic Card
Each card (BRD43ZAMC) has 32 bi-coloured LED’s which can be used to display the status of up to
32 Zones. The zone numbers assigned to each LED are configurable and the LED’s will operate in
the following manner for the respective zone statuses:
ZONE STATUS
LED STATE
LED COLOUR
FIRE
ON STEADY
RED
DEPENDENCY B
FLASH
RED
DISABLED
ON STEADY
YELLOW
FAULT
FLASH
YELLOW
ALL OTHER
OFF
n/a
The card will also respond to a lamp test when instigated on the panel to which it is connected.
Figure 77: 64 Zone Indicator Decal
When more than 64 zone indicators are required the Zone Mimic Card board will be fitted to
ENC1824 and fitted to the individual Cut Outs provided on the SP8 front door
Figure 78: DEC1515-T2 Zone Indicator Decal (See LAB1516.doc for Slip in Label)l
Fit EOL Termination Link
if Last Module
on Comms Bus
In
Out
Address SW
(See Note)
1 2 3 4
ON
C
N
1
C
N
2
RS485 Control
/ 27VDC
Comms In
Top Card &
PCB Securing Clips
Bottom Card &
PCB Securing Clips
RS485 Control
/ 27VDC
Comms Out
Figure 79: Zone Alarm Mimic Card Rear View showing connectors and Address Switch
Note: See Section 17 for Addressing Details (SW1)