Specifications

Page 49
EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION
9 Incoming Fire Alarm Signal
Will operate the red common LED fire indicator
Will display location of fire alarm origin on the LCD
Will activate external alarm.
Will activate the internal FACP buzzer.
Will activate any ancillary equipment so programmed.
Will abort any test in progress.
The LCD will always display the first fire alarm signal received in the top section of the LCD. The
lower section of the LCD will also permanently display the most recent zone in alarm. Other essential
fire alarm information and fault or disablement information is available via the
buttons. After 30 seconds if no button is pressed the top section of the
display will revert to displaying the first zone in alarm.
DETECTOR 1 SMOKE
L1 S1 Z17 ALARM
01/01/2012 16:15:10
SENSOR ALARMS 1 OF 5
**************CURRENT ALARM************
DETECTOR 5
L1 S5 Z17 ALARM 01/01/2012 16:14:50
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Figure 71: LCD Screen with 5 Devices in Alarm
Note: The displayed information changes to that associated with the device as the
push buttons are pressed. If there is a fault condition or a fire alarm and
the buzzer is sounding, press the button to stop it sounding