Specifications

Page 42
EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION
8.6 I/O
Press To display the Manual I/O Control menu
MANUAL I/O CONTROL
0: INPUT 1 :OUTPUT
2: REMOVE ALL MANUAL CONTROL
SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Figure 60: The Manual I/O Control Menu
Manual I/O control allows the technician to turn ON or OFF inputs and outputs off a device to
facilitate testing or isolation of plant during maintenance. Removal of manual control returns control
to the panel.
Press
Input Selected:
Press
IN A PANEL: Enter the I/O Controller number then the input number. This will display the
description for the input and its current state, you can then turn the input ON or OFF or remove
manual control.
ON A LOOP: Enter the loop number, the device number and the input number. This will display
the description for the input and its current state, you can then turn the input ON or OFF or remove
manual control.
Remove All Manual Input Control: Will remove all manual input control.
Output Selected: Same sequences as above for inputs but substitute outputs for inputs.
Remove All Manual Control Selected: Globally removes all manual control.