Specifications
Page 41
EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION
8.5 TESTS
Press to access the TESTS menu. Note this is an Access Level 3 function only.
TESTING MENU
0: WALK TEST 1:LOOP TEST
SELECT NO.
AC:3Z ALM:0 PALM:0 FLT:0 DIS:0
Figure 59: The Testing Menu
Press Is pressed to initiate a WALK TEST:
Press LOOP TEST requires the operator to select a LOOP for DIAGNOSTIC TESTING
Entering the LOOP number and pressing will initiate the DIAGNOSTIC TEST.
Note: The LED’s on the Brigade Board will indicate which leg is being tested.
The tests displayed are;
TESTING SIDE A IDENTIFING DEVICES on SIDE A, and
TESTING SIDE B IDENTIFING DEVICES on SIDE B.
Once the testing is completed the final screen will display the number of devices found and tested on
the LOOP and a Reset is requested to return the system to normal.
Note: If the data is not entered within 2 minutes the screen will time out and return to the
DEFAULT SCREEN.
Note: A Loop Test needs to be conducted after a short / open circuit has occurred, corrected
and cleared to return the panel to its default Normal status otherwise the panel will display a loop
fault.