6 Functions And Menus
IMPORTANT NOTE: It is strongly recommended that all field programming changes be
properly recorded.
6.1 The Default LCD Display
In its normal state the FireFinder PLUS will display a screen similar to that shown below.
FIREFINDER 17/12/2012 09:00:00
FIREFINDER PLUS SUBMISSION
BY AMPAC TECHNOLOGIES
SYSTEM IS NORMAL
AC:2Z ALM:0 PALM:0 FLT:0 DIS:0
Figure 23: The Default LCD Display
This screen can be configured with the servicing company’s name and phone number via a laptop or
modem. The current date, time is set in the Function menu while system status is automatically
displayed.
6.2 LCD Contrast
The Contrast can be adjusted using a combination or the button the and
buttons.
Keep the 'Display' button pressed while simultaneously pressing the '<' button to take the contrast
down 1 level, the '>' to take up the contrast by 1 level, the '<<' to take the contrast down by 8 levels
or the '>>' to take the contrast up by 8 levels.
Note: This button combination will only work in access level 2 or higher.
6.3 Accessing Functions and Menus
At Levels 2 and 3, access to the panel Functions are password protected.
A new panel has a pre-programmed password of 2222 for Level 2 and 3333 for Level 3.
Note: Only Authorised Service Technicians / Engineers have the ability to change passwords.
Note: All menus are provided with screen prompts and a “Quick Reference Guide” (see Section
xx) guides the operator through the operation of the FACP.
From the DEFAULT DISPLAY, press MENU or FUNCTION. The FUNCTION menu is
password protected (actually a pass-number as it can only contain numbers) to prevent unauthorised
changes to the panel's configuration.