Specifications
Page 17
EN54 FIREFINDER PLUS INSTALLATION,COMMISSIONING & OPERATION
4.8.5 Relay Output Connections
Five “voltage free” relay outputs (TB2 – TB6) are provided and can be configured for a variety of
uses.
Alarm - activated on device alarm conditions and “Function” programmed logics. The relay
is turned off during a FARE disable condition.
Sprinkler - activated on device alarm conditions and “Function” programmed logics.
Fault - activated on all fault conditions and “Function” programmed logics. The relay is
turned off during a FWRE disable condition.
Isolate - activated on all isolate conditions and “Function” programmed logics.
Battery Fail - activated on battery fail conditions and “Function” programmed logics.
EWIS - activated on evacuation, device alarm conditions and “Function” programmed logics.
If the activation of this relay is due to an evacuation condition, then the relay is turned off
during an Alarm (sounder) disable or Alarm (sounder) silence condition.
AUX / ANC - activated on device alarm conditions.
General Purpose - activated via “Function” programmed logics
These outputs have been designed to be able to switch predominately resistive loads as listed
below.
Switching voltage
Maximum switching current
30VDC
1A
24VAC
1A
50VDC
250mA
40VAC
250mA
The relay contacts are connected as shown below.
TB2
TB3
TB4
TB5
TB6
TB2 to TB6 are located on the
lower left hand side of the board
C
NC
NO
1A Un-monitored
Voltage Free Conacts:
NO: Normally Open
NC: Normally Closed
C: Common
NO C NC
NO C NCNO C NC
NO C NC
NO C NC
NO C NC
NO C NC
Note:
N1236
NO C NC
NO C NC
FIRE
FAULT
EWIS
ISOLATE
BATT
FAIL
Relays are Programmable. Default Setup Shown
Figure 15: Relay Outputs