Specifications

Ampac Technologies Pty Ltd
FireFinder
TM
Operators Manual
PAGE 30
DOC No:G0109WO1.doc DIR: L:\MANUALS DATE: 30/11/00 REVISION: 3
7.6.2 Testing Menu
Fig 25: The Testing Menu
This menu is selected by pressing 5 while on the Main Menu. From here the following can be tested
0. Alarm Test: Alarm tests either a zone or a sensor or a range of zones or sensors.
1. Fault Test: Fault tests either a zone or a sensor or a range of zones or sensors.
2. System Test: Will perform a system test ( a basic test of all parts in the system)
3. Lamp Test: Will flash the LED’s on the front panel and test the LCD display.
7.7 Function Menu
The function menu provides access to many programming and configuration functions. These features
are protected by a password (actually a pass-number as it can only contain numbers) to prevent
unauthorised tampering with the panel's configuration. A new panel will have the password 3333 already
programmed so that you can enter your own.
To get to the functions menu press FUNCTION while the panel is on the Default Display. You must then
enter a password. Three levels of password have been defined so that access to certain facilities can be
restricted (such as the ability to enter new passwords).
Level I: Allows access to:
Date: Enter the Day, Month and Year (4-digit year).
Time: Enter the hours (24-hour mode) and minutes.
Day/Night Settings: Not currently active.
Logs: Alarm and Fault logs.
Tests: Walk and loop tests.
Level II: In addition to the level I facilities, adds the following:
I/O
Programming
Level III: In addition to the level II facilities, adds the following
Password
Fig 26: The Level III Functions Menu
TESTING MENU
0: ALARM 1: FAULT 2: SYSTEM 3: LAMP
SELECT No.
LEVEL III MAIN FUNCTIONS
0: DATE 1: TIME 2: DAY/NIGHT SETTINGS
3: LOGS 4: TESTS 5: I/O 6: PROG 7: PASSWORDS
SELECT No.