7.6 The Main Menu
Fig 23:The Main Menu
From the main menu the user is able to view any Acknowledged alarms on the system. You can also
view any pre-alarms, faults or isolates on the system. If there are no alarms, faults or isolated zones or
devices, a message will display for about a second and the display will then return to the previous menu.
7.6.1 Status Menu
Fig 24: The Status Menu
Press 4 while on the Main Menu to display the Status Menu.
From the status menu you can interrogate the status of all of the system components and settings listed
below
0. Loops: Enter the loop number and it will display its status.
1. Modules: Enter the module number and it will display the type, the software version and its status.
2. Supply: This will display the charger voltage, whether or not the power supply is in fault, and if the
battery is correctly fitted.
3. Brigade: This will display the status of all of the brigade relays and outputs on the brigade board.
4. I/O: Can display the status of the input output in a panel or on a loop. You must enter the I/O module
number, then the input or output on that module (or the loop and sensor number and the output on
that device) it will then give you a description of what that input or output does and tells you its
current state.
5. Network: Display the status of the network.
6. System: This will display the status of the system. eg Faults, Alarms, Isolates.
7. A values: This will display the analog value being returned by a detector. It will display the
description of the detector, as well as its type, its state and the Raw Analog Value in counts.
STATUS MENU
0: LOOPS 1: MODULES 2: P/SUPPLY 3: BRIGADE
4: I/O 5: NETWORK 6: SYSTEM 7: AVALUES
SELECT No.
MAIN MENU
0: ALARMS 1: PREALARMS 2: FAULTS
3: ISOLATES 4: STATUS 5: TESTING
SELECT No.