Specifications
FIREFINDER NZ 
CONFIGURATION MANAGER 
10  Hardware requirements 
The FireFinder Series II can be configured and updates to the software made via the serial port 
(RS232) on the Main Board (302-674). 
If  you  are  using  a  PC  running Windows  you  can  use  AMPAC’s  ConfigManager  program  to 
communicate with the FireFinder Series II. Connect the FACP serial port (CN8) to one of the serial 
ports on your PC 
PIN 1 
PIN 1 
PIN 1 
TD 
RD 
SHIELD 
TD 
RD 
TD 
RD 
SHIELD 
25 PIN MALE DB25 CONNECTOR 
9 PIN MALE DB9M 
 CONNECTOR 
10 WAY IDC 
CONNECTOR 
To  
FireFinder™ 
CN8 on 302-674 
Main Board 
To PC or Laptop Computer COM Port 
1
2
3
4
5
6
7
8
9
DB9F CONNECTOR
2 CORE SHIELDED CABLE
DB9F CONNECTOR
1
2
3
4
5
6
7
8
9
Rx. Data
Tx. Data
Tx. Data
Rx. Data
Shield
Shield
Female Rear View
Female Rear View
Figure 80: FireFinder Series II Debug Cable Connections 
The connector on the: FireFinder Series II
may be either the 10 way (older versions) or the DB9F 
connector on later versions, select the one that is appropriate to the system. 
Note: the DB9F to DB9F cable is not sensitive to which end is plugged in to the FireFinder 
Series II or serial port of the PC or vice versa. 
The connections between the PC/Modem and the panel are crossed. i.e. TD connects to RD.  
Make sure the ConfigManager program is set to use the port you have connected the cable to and 
set up the configuration as follows:  
Bits per second:     38400 
Data bits:      8  
Parity:        None  
Stop bits:       1  
Flow Control:      None  