Specifications
FIREFINDER NZ 
CONFIGURATION MANAGER 
7.6  Data Output 
The data output consists of a string of characters as detailed: 
Format 1: <state1><state2><state3><state4>G<group><cr><lf> (No Descriptor string available) 
Format  2:  <state1><state2><state3><state4>  Z<zone><cr><lf>  (Descriptor  string  available  for 
conventional zones. If a group of sensors share a common zone number but not with a conventional 
zone then no descriptor is available). 
Format  3:  <state1><state2><state3><state4>  L<loop>S<sensor><cr><lf>>  (Descriptor  string 
available for Loop and sensor. 
<state1>N = no alarm, A = alarm 
<state2>N = no prealarm, P=prealarm 
<state3>N = no fault, F = fault 
<state4>N = no isolate, I = isolate 
G<group>= Group number of the device 
Z<zone>= Zone number of the device 
L<loop>= Loop number of the device 
S<sensor>= Sensor number of the device 
<cr> carriage return character ($0D) 
<lf> line feed character ($0A) 
Three options are available to select which formats are used 
7.6.1  Option 1 - Physical Output Enabled 
Uses Format 2 or 3, depending if the device that changes state is a zone or sensor. If a sensor is 
also  "zoned",  then  if  the  change  in state of  that  sensor also changes  the  state  of  the zone,  two 
updates will be sent, one for the sensor (Format 3) and one for the zone (Format 2)  
>ANNNZ5  Zone 5 goes to alarm on the main panel 
>NNFNL1S3  Loop 1 sensor 3 into fault 
7.6.2  Option 2 - Physical and Logical Output Enabled 
Uses Format 1 and 2 or 3. 
If a device is not "grouped" then the Format 1 update is not output. 
7.6.3  Option 3 - Logical Output Enabled 
Uses only Format 1. 
Note: Ungrouped devices DO NOT cause any output at the BMS module. 
Note: in all cases, leading zeros are truncated. All characters are ASCII, with the 8th bit clear. 