Specifications
FIREFINDER NZ 
CONFIGURATION MANAGER 
4.4.2  Brigade Signaling Board 
Figure 22: Panels Settings - Brigade Signaling Board 
Fitted: Click on the box (ticked) if the board is fitted. (Default selected) 
Alarm relay normally energised: If the relay is to be normally energised click on the check box 
(ticked). (Default not selected) 
Fault Relay normally energised: If the relay is to be normally energised click on the check box 
(ticked). (Default selected) 
Monitor Warning output: If ticked Monitor this O/P. (Default not selected) 
Monitor Fault O/P: If ticked Monitor this O/P. (Default not selected) 
Monitor Bell O/P: If ticked Monitor this O/P. (Default selected) 
Monitor  Auxiliary  O/P:  Click  on  the  check  box  (ticked)  if  O/P  is  to  be  monitored.  (Default  not 
selected) 
Door Switch Fitted: Ticked if Door Switch fitted (Default Selected) 
SGD Fitted: Ticked if a Signal Generating Device is Fitted (Default Selected) 