Specifications
Page 66 
FIREFINDER SERIES II    INSTALLATION,  COMMISSIONING  & 
OPERATION 
After scrolling through the groups and entering what I/O GROUPS will be turned 
on by  what module/s or device/s in  a zone/s the  operator is prompted to press 
ENTER to confirm the entries and / or changes. 
10.8.2  Device Programming 
Press  DEVICE: 
Use these keys to EDIT and move through wording & numbering 
Use these keys to MOVE between fields i.e.: DESC & TYPE and next parameter 
Enter the Loop and Sensor number then scroll through the following screens. 
Press    or  Press 
 To EDIT  or   to DELETE 
1. EDIT LxSx DESCRIPTION AND TYPE STRING.  Edit then.  Press     
e.g.:  DESC    Loop 1 Sensor 1 
TYPE    SMOKE 
2. Allocate / Edit the Sensor to a Zone and set the device type then.  Press     
e.g.: XP95 Photo, XP95 Heat etc- 
3. Set /Edit and display the Output Configurations or options then.  Press     
e.g.: Latching, AVF, Non-latching etc 
4. Set / Edits and enables / disables the day/night settings then.    Press     
5. Allocates / Edits the Loop and Sensors Groups.           
After  scrolling  through  the  groups  a prompt  tells  the  operator  to  press  ENTER to  confirm  the 
changes. 
10.8.3  Input Programming 
Press INPUT:  
By following the screen prompts as above Edit or Delete an INPUT in a panel or a loop.  
Screen: PROGRAM MENU SELECTING AN INPUT 
 IN A PANEL 
 ON A LOOP 
I/O MODULE 
LOOP 
Select I/O MODULE NO. then ENTER 
Select LOOP NO. then ENTER 
INPUT 
SENSOR 
Select I/P NO then ENTER 
Select SENSOR NO. then ENTER 
EDIT / DELETE DESC 
INPUT 
Select INPUT NO. then ENTER key 
ALPHA KEYS ARE ACTIVE 
EDIT Lx Sx I/Px DESC STRING DESC 