Specifications
Page 53 
FIREFINDER SERIES II    INSTALLATION,  COMMISSIONING  & 
OPERATION 
7  FireFinder Control Panel 
MENU
FUNCTION
POWER ON
PRE-ALARM
TEST MODE
SOUNDER STATUS
SUPPLY FAULT
FIRE
ZONE
SENSOR
LOOP
DISPLAY
TO
1
4
7
ABC
JKL
TUV
2
5
8
0
DEF
MNO
WXYZ
SPACE
ENTER
3
6
9
GHI
PQRS
SYMB
DEVICE
DISABLE/ENABLE
SOUNDER
SILENCE
EVACUATE
PREVIOUS
NEXT
BUZZER
SILENCE
RESET
INDICATOR
TEST
FAULT
DISABLED
'2'
LCD WINDOW
CANCEL ENTRY
EARTH FAULT
SYSTEM FAULT
F.W.R.E. ACTIVE
F.A.R.E. ACTIVE
F.W.R.E. FAULT
F.A.R.E. FAULT
Figure 58: The FireFinder Control Panel with an 8 Line LCD 
Controls & Indicators 
FIRE
 (Red): This LED will be illuminated steady if any fire alarms are present on the system. 
FAULT
  (Yellow): This  LED  will  be  illuminated  steady if  there are  any faults  on  the system, 
whether they are loop faults, module faults, device faults etc. 
DISABLED
 (Yellow): The LED  will light steady if any detectors, devices or zones  in the system 
have been disabled or if an output relay has been de-activated. The display will show the conditions 
as per EN54 9.2 and 9.4.2 
SOUNDER
SILENCE
 (Yellow): Pressing this button will silence any Bells or Sounders (activated either by a 
fire alarm, a manual evacuation or a manual alert) that are connected to the fire panel. If the bells or 
sounders are silenced the LED just above the button will be illuminated steady indicating that the 
sounders have been silenced and a sounder resound is available.  If a manual evacuate or manual 
alert condition is present when the Sounder Silence button is pressed, these conditions will remain 
visible indicating the conditions are still present for resounding. A new Fire Alarm, manual evacuate 
or  manual  alert  will  resound  all  the  previously  silenced  Bells  and  Sounders.  Pressing  Sounder 
Silence a second time while the Sounder Silence LED is illuminated, will also re-sound the Bells and 
Sounders. 
EVACUATE
 (Yellow): Pressing this  button  will activate  the Sounders and  Bells  that have been 
programmed for manual evacuation and the LED just above the button will be illuminated steady. If 
the sounders have been previously silenced the LED above the Sounder Silence button will turn off 
and  the  Sounders  and  Bells  that  were  previously silenced  will resound.  This  manual  evacuate 
condition can only be cleared by a Reset and will override a manual “Alert” condition. 