Installation Instructions Regal Series Power Columns Corporation
Note Power column installation should conform to local building codes The installation instructions provided is for the Amico standard products. Slight modifications to the installations may be required. The product shipped to the job site may not be exactly as shown on the installation drawings.
Before Installation 1. Review a copy of the final approved shop drawing(s) and/or submittal package. These documents will provide you with technical information specific to your installation, such as: - equipment types & quantities - room numbers and location - shop drawings of each unit type - wiring diagrams and rough-in locations 2. Locate the power column from the shipping boxes that you wish to install. The contents of each shipping box are listed on the shipping document(s). www.amico.
Installation 2. Remove laminate panels from power column (using tool provided) by lifting panels vertically until resistance is felt, then rotate bottom of panel out and pull down. Be careful not to drop panel.
2. Refer to following figures to complete installation. “C” channel power column A = 6.750” (171.5mm) for 9” PC A = 9.875” (251mm) for 12” x 9.5” PC A = 17.375” (441.3mm) for 19” x 9.5” PC A = 24.25” (616mm) for 28” PC A = 9.5” (241.3mm) for 12” x 12” PC A = 17” (432mm) for 19” x 19” PC Figure 2 structural ceiling “A” anti-sway support structure (supplied by others) finished ceiling base “C” channel typ. of 2 threaded rod typ. of 4 (by others) power column Figure 3 Figure 1 www.amico.
3. Anchor base of column to floor (hardware by others). Note that base does not have to be removed to complete this step. See figure 1. 4. Structural bracket(s) and hardware to attach to Amico column are to be supplied and installed by others (see figure 3). Amico provides 2 “c” channels attached to the column to mate with this structural support (see figure 2). 5.
www.amico.com Amico Architectural | www.amico.com 85 Fulton Way, Richmond Hill Ontario, L4B 2N4, Canada 71 East Industry Court, Deer Park NY 11729, U.S.A Toll Free Tel: 1.877.264.2697 Toll Free Fax: 1.866.440.4986 Tel: 905.763.7778 Fax: 905.763.8587 Email: info@amico.com C US LISTED INSTALL INSTR.