Owner's manual

34 Amico Pipeline
Appendix C
Wiring Schematic Heater Units
The Heaters normally switch on when the temperature drops below 24°C or 75°F. If the temperature exceeds 65-75°C or
160-175°F, the Heater re-set switch will trip and the Heaters will automatically switch o. To re-set the Heaters, remove
the Heater covers & press the Red button on the re-set switch to activate. When the Heaters are in use or switched on, it
will draw up to 3 amps of current. The Heater Cartridge is 200Watts (each side). Normally both sides do not switch on
together, it depends on the ow of gas or climatic conditions.
Inlet Pressure
Block
Power Supply
Reset Switch
Heater Cartridge
Wires
Reset Switch
Inlet Pressure
Bloc
Heater Cartridge
(Inside Inlet Pressure Block)
Heater Cartridge
(Inside Inlet Pressure Block)