3.6 Auxiliary I/O Interface
A9240-A-001-485 RFID reader provides 1 set of auxiliary input and four sets of auxiliary
outputs. All auxiliary I/O are optically isolated. The +V and –V terminal blocks must be
connected to +12V DC and ground in order for the auxiliary I/O to function properly. Other
voltage level should not be used. User sensors, alarms, warning lights, or PLC
(programmable logic controller) can be connected to the A9240-A-001-485 RFID reader to
form a flexible infrastructure.
Optically Isolated Input
The optically isolated input terminals (IN1) are to be connected to external switch only. The
external switches are either open or close. There should not be any voltage or current
draining / supply on these contacts. The reader will sense the states of the external switch
on these input terminals by means of optical coupler. The second set of optically isolated
input terminals (IN2) is reserved for future usage. This auxiliary input should not be used.
Please contact AMIC regarding the usage of input terminals, IN2.
Optically Isolated Output
There are four sets of optically isolated output ports. Each output port consists of two
terminals. Each output port’s terminals are either connected or disconnected through the
internal relay controlled by optical coupler. The electrical characteristics of the relay are
described as follows:
Relay Contact capacity (Resistive load): 3A/125VAC or 3A/30VDC
Relay Contact capacity (Inductive load): 0.3A/125VAC or 0.3A/30VDC
Relay Contact resistance: 100m
Ω
Max.
Relay Operation time: 5msec Max.
Relay Release time: 5msec Max.
Max. Relay ON/OFF switching (Mechanically): 300 operation/min
Max. Relay ON/OFF switching (Electrically): 30 operation/min
General specifications
Isolation: 5000 Vrms