Specifications

DISCOVER YOUR DIGITAL POTENTIAL
5
SPECIFICATIONS
I/O
Analog input x 2: 0-2.5V, 0-10V / 4-20mA (SW configurable)
Digital input x 2
RS485 Half-Duplex
Communication
900MHz RF star-network configuration for multiple pumps
connectivity
Measurements
3-Axis vibration monitoring [Inch/Sec]
Temperature ±5° [°F]
Battery voltage [V]
EDGE computing
Spectral analysis
o Radial velocity RMS
o Axial velocity RMS
o 3-Axis velocity FFT @ Five selected frequencies
Where x = rotation freq. ex. 1x, 2x, 3x, 7x, 10x
o Rotation velocity [RPM]
Impact analysis
o Stroke count
o Stroke rate
Operational hours
Notifications
Axis velocity RMS threshold cross
Radial velocity RMS threshold cross
Velocity amplitude threshold cross in any of the FFT selected
frequencies
Stroke rate threshold cross
Stroke count threshold cross
Operational time threshold cross
Temperature threshold cross
Analog measurement threshold cross
Digital inputs changes or flow frequency threshold cross
Operation modes
Battery: 1 yr. @ 4 sample/hour and 2 cloud updates per day
External DC power: 9..24VDC; up to 20 sample/hour and 8 cloud
updates per day
User interface
Internet browser
Mobile apps: IoS and Android using BLE for on-site offline device
connectivity
Dimension & build
3.3 Diameter, 2.0 Height
Robust glass filled PP enclosure IP66 comply
Mounting neck ½” NPT male thread x ¾” long
Standards
FCC Part 15 (see label)
RoHS comply
Environmental conditions
Temperature: -22°F/+158°F