Owner's manual
11
2.13 - Byte Ordering
In the Modbus slave confi guration, data can be ac-
cessed as integers (16 bits), long integers (32 bits), 
and fl oating point value (32 bits). The order that the 
bytes are sent must be known by the master in order to 
assembly the bytes into the correct value. Byte order-
ing can have a few different terminologies. 
1) Big/Little Endian.
2) Byte order by number, with 1 indicating the most 
 signifi cant part of the value, and 4 the least signifi -
 cant.
3) Word/Byte, indicating which word (16 bits, high or 
 low) is sent fi rst, and which byte of the word (high or 
 low) come fi rst in that byte.
See the following example for accessing a product 
reading of 46.60 inches. The integer value will be 
4660, which translates to the hex number 0x00001234.  
The individual bytes, 0x00, 0x00, 0x12, and 0x34 can 
be sent the following 4 ways for 32 bits values:
1) Big Endian, Byte order 1234, High Word High Byte 
 (HWHB) Order sent: 0x00, 0x00, 0x12, 0x34
2) Little Endian, Byte order 4321, Low Word Low Byte 
 (LWLB) Order sent: 0x34, 0x12, 0x00, 0x00
3) Big Endian Byte Swapped, Byte order 2143, High 
 Word Low Byte (HWLB) Order sent: 0x00, 0x00, 
 0x34, 0x12
4) Little Endian Byte Swapped, Byte order 3412, Low 
 Word High Byte (LWHB)
 Order sent: 0x12, 0x34, 0x00, 0x00
The individual bytes 0x12, and 0x34 can be sent the 
following 2 ways for 16 bits values:
1) Big Endian, Byte order 12, High Byte fi rst (HB)
 Order sent: 0x12, 0x34
2) Little Endian, Byte order 21, Low Byte fi rst (LB)
 Order sent: 0x34, 0x12
2.14 - Modbus Map
Use the following tables to fi nd the register number 
for the desired format. First, go to the section for the 
number format you desire (integer, long integer, or 
fl oating point). Then fi nd the table with the desired 
units, English or metric. Then fi nd the value (product, 
interface, average temperature, etc) in the left hand 
column. Next, fi nd the desired byte ordering across the 
top row. The corresponding entry at the intersection of 
these 2 items gives the register that should be specifi ed 
in the Modbus master request message. The number 
of registers needed to obtain the value is also specifi ed 
for each format.
NOTE:
HWHB = High Word High byte
LWHB = Low Word High Byte,
HWLB = High word low byte
LWLB = Low Word low byte
2.15 Modbus Registers
Integer (16 bit Signed) formats
Signed 16 bit Integer, 16 bits of data per register, 
1 register needed to get value English Units, 
inches and degrees F
Data Big Endian,/ 
 Hi Byte fi rst 
Little Endian/
Low Byte fi rst
Product 31803 32003
Interface 31805 32005
product temperature  31807 32007
interface temperature  31809 32009
average temperature  31811 32011
status 31813 32013
Span 31815 32015
temperature 1   31817 32017
temperature 2 31819 32019
temperature 3  31821 32021
temperature 4  31823 32023
temperature 5  31825 32025
max temperature  31827 32027
temperature sensor 1 location    
(closest to bottom)
31829 32029
temperature  sensor  2  location  31831 32031
temperature sensor 3  31833  32033
temperature  sensor  4  location  31835 32035
temperature sensor 5 location 
(closest to top) 
31837 32037
Software version 31899 32099
Data Big Endian,/ 
 Hi Byte fi rst 
Little Endian/
Low Byte fi rst
Product 31903 32103
Interface 31905 32105
product temperature  31907 32107
interface temperature  31909 32109
average temperature  31911 32111
status 31913 32113
Span 31915 32115
temperature 1   31917 32117
temperature 2 31919 32119
temperature 3  31921 32121
temperature 4  31923 32123
temperature 5  31925 32125
max temperature  31927 32127
temperature sensor 1 location    
(closest to bottom)
31929 32129
temperature  sensor  2  location  31931 32131
temperature sensor 3  31933  32133
temperature  sensor  4  location  31935 32135
temperature sensor 5 location 
(closest to top) 
31937 32137
Software version 31999 32199
Signed 16 bit Integer, 16 bits of data per register, 1 
register needed to get value Metric Units, 
centimeters and degrees C