Manual
16
Installation and Programming Manual
Chapter 3: Mounting and Wiring
L2
100-240VAC 50/60HZ
POWER SUPPLY
POWER
1
L1
PROBERELAY
4 3 2 1
C.P.U.
FLT CHK
AUX INP
FMPS01
}
}
4523
GND
67
FMIP01
FMOR01 FMMP01
POWER 4 3 2 1
PIN SIGNAL NAME DIRECTION
GND CHASSIS1
RXD RS-2322 OUTPUT
TXD RS-2323 INPUT
NO CONNECTION4
GND SIGNAL5
TX2+ RS-485
6 +I/O
RTS RS-2327 INPUT
CTS RS-2328 OUTPUT
TX2- RS-4859 -I/O
87564
78
546
312
RELAY
312
PROBE
21
L1
L2
NO
NO
L1
L2
INPUT
POWER
FAULT
CHECK
AUXILIARY
INPUT
NO
NO
NC
NC
NO
NO
NC
NC
UPPER
LIMIT
LOWER
LIMIT
RELAY CONTACT RATINGS :
8A 250VAC 30VDC
1/4 HP 125, 250VAC
PIN 1
PIN 5
PIN 6
PIN 9
SHEILD TO CASE ASSEMBLY
CABLE ASSEMBLY
(P/N SD0439700)
MAGNET ASSEMBLY
SERIES 951VP-2110
LINEAR TRANSDUCER
RED
BLACK
BLUE
BROWN
WIRE COLORS PROBE CONN.
INPUT-
INPUT+
+24VDC
GROUND
RELAY CONTACT RATING :
8A 250VAC 30VDC
1/4 HP 125, 250VAC
AUXILIARY INPUT RATING
:
85-256VAC @ 12mA
POWER INPUT RATING :
85-265VAC @ 450mA
INPUT+
INPUT-
PIN C
PIN B
PIN F
PIN E
FAULT CHECK
UPPER & LOWER LIMIT
PROGRAM
SECURITY
AUX POWER
AUX 3 INPUT
AUX POWER RATING :
+24VDC @ 15mA
AUX 3 INPUT RATING :
SINKING DEVICE, +5VDC MAX
ON AT < 1VDC @ 2mA
P
R
O
B
EY
A
L
E
R
PROGRAM SECURITY INPUT
SWITCH CLOSED ENABLES PROGRAM MODE
INPUT+ INPUT-
OR
PROGRAM
(CLOSED)
DIAGRAM 1
SINKING DEVICE, +5VDC MAX
ON AT < 1VDC @ 0.2mA
SEE DIAGRAM 1 FOR SUGGESTED CONNECTIONS
50-60 Hz
INSULATE AND TIE BACK
ALL UNUSED WIRES
3 68745
PROBE
21
WIRE COLORS
BROWN
BLUE
BLACK
RED
PIN F
ALL UNUSED WIRES
INSULATE AND TIE BACK
PIN E
PIN B
PIN C
PROBE CONN.
MAGNET ASSEMBLY
(P/N SD0439700)
LINEAR TRANSDUCER
SERIES 951 OR 952 CP, RS OR VPE
CABLE ASSEMBLY
WHITE
GRAY PIN K
PIN A
CUSTOMER
DC POWER
SUPPLY
OPTIONAL
-
+
FMIP02
6mA MAX.
5-24VDC
SEE NOTE 1
SHEILD TO CASE ASSEMBLY
FMIP01
NOTES: UNLESS OTHERWISE SPECIFIED
1. REQUIRED FOR RESET TO PRESET ONLY.
WARNING: SEE NOTE 2.
2. WARNING: DO NOT CONNECT A 951 CP OR
TO PROBE WILL RESULT.
RS PROBE TO FM1P01 INPUT CARD. DAMAGE
Figure 3-11 LDT - Based System Wiring Diagram