Appendix A: Error Messages
53
Installation and Programming Manual
Appendix A: Error Messages
The following errors will cause the upper and lower limit relays to de-energize:
Chart A-5 Upper and Lower Limit Relay Errors
The following chart contains a resolver-specic error:
Chart A-6 Resolver-Specic Error
Error Displayed Error Description
SEr320 This is a resolver-specic error. See Chart A-6.
SEr330 The input device is not connected to the monitor's input module.
SEr331 This is a LDT-specic error. See Chart A-7.
OEr101 The press's ram did not move within the time programmed in the Move
Detection Time-Out function.
OEr330 or
OEr320
The press's shut height moved beyond the value programmed in the Nega-
tive Over Travel Limit functions.
Error Displayed Error Description Solution
SEr320 The cable may not be connected, an
open or short may exist in the cable,
or the resolver's primary may be
open or shorted.
To determine the exact condition,
enter the Error Conditions function
(306). For instructions, see Error
Conditions (306) following this
chart.