Appendix A: Error Messages
53
Installation and Programming Manual
Appendix A: Error Messages
The following chart contains errors that will cause the fault check relay to open:
Chart A-4 Fault Check Relay Errors
Error Displayed Error Description Solution
EEr 1 An invalid function number was
entered.
Enter a valid function number.
EEr 2 An invalid system conguration was
entered.
Enter a valid system conguration.
EEr 3 A value outside the function's ac-
ceptable range was entered.
Review function's range and re-en-
ter value.
EEr 4 An incorrect parameter was entered. Contact GEMCO Tech. Support.
EEr 5 A value was programmed into the
Lower End Limit function that is
greater than the value programmed
in the Upper End Limit function.
Program a value that is less than
the value programmed in the Upper
End Limit function.
EEr 6 The value programmed into the Up-
per End Limit function is less than
the value programmed in the Lower
End Limit function.
Program a value that is greater than
the value programmed in the Lower
End Limit function.
Chart A-3: Entry Errors
Error Displayed Error Description
SEr101 A conguration error occurred.
SEr106 Firmware CRC error occurred.
SEr320 This is resolver-specic error. See Chart A-6.
SEr330 The input device is not connected to the monitor's input module.
SEr331 This is an LDT-Specic Error. See Chart A-7.
OEr101 The press's ram did not move within the time programmed in the Move
Detection Time-out function.
OEr330 or
OEr320
The press's shut height moved beyond the value programmed in the Nega-
tive Over Travel Limit function.