Venting Guidelines for Category I Gas Appliances
Single-Appliance Vent - Tables 1 and 2 (continued)
10. Vent connectors shall not be upsized more than two sizes greater than the listed appliance
categorized vent diameter, flue collar diameter, or draft hood outlet diameter.
11. In a single run of vent or vent connector, more than one diameter and type shall be permitted to be
used, provided that all the sizes and types are permitted by the tables.
12. Interpolation shall be permitted in calculating capacities for vent dimensions that fall between table
entries. (See Example 3.)
13. Extrapolation beyond the table entries shall not be permitted.
For SI units, 1 inch = 25.4 mm; 1 foot = 0.305 m; 1000 Btu/hour = 0.293 kW; 1 inch
2
= 645 mm
2
.
14. For vent heights lower than 6 feet and higher than shown in the tables, engineering methods shall be
used to calculate vent capacities.