Instruction manual

Page 18 of 32 OM 751
Priority Result
Application Override Input Unit Mode Override Input Unit Mode Output
Heat
Normal (Auto) Cool
Emergency Heat
Heat Heat
Normal (Auto) Cool Cool
Night Purge Night Purge
Off Off
Emergency Heat Emergency Heat
Fan Only Fan Only
Heat Dont Care Heat
Cool Dont Care Cool
Night Purge Dont Care Night Purge
Off Dont Care Off
Emergency Heat Dont Care Emergency Heat
Fan Only Dont Care Fan Only
Normal (Auto) is the normal UVC power-up state.
These are network variables.
Table 10. Normal UVC Mode Priority
Occupancy Modes
The UVC is provided with four occupancy modes: Occupied, Standby,
Unoccupied, and Bypass. The occupancy mode effects which heating
and cooling temperature setpoints will be used, effects IAF operation,
and effects OAD operation. The Manual Adjust Occupancy and
Networked Occupancy Sensor network variables, along with the
Unoccupied and Tenant Override binary inputs, are used to determine
the Effective Occupancy.
Priority Result
Emergency Override Remote Shutdown Energy Hold Energy Hold Unit Mode Actual UVC
Input Binary Input Off Input Off Output Output Action
Normal Normal
See the Normal
Normal
De-energized
UVC Mode Priority table
Energy Hold Off Energy Hold Off Off Off
Energized Dont Care Energy Hold Off Off Off
Pressurize Dont Care Dont Care Dont Care Off Pressurize
De-pressurize Dont Care Dont Care Dont Care Off De-pressurize
Purge Dont Care Dont Care Dont Care Off Purge
Shutdown Dont Care Dont Care Dont Care Off Off
Normal here indicated the UVC power-up condition.
De-energized here means that the contacts connected to this binary input are open.
Energized here means that the contacts connected to this binary input are closed.
These are network variables.
Table 9. Special Purpose UVC Unit Mode Priority
Table 11. Occupancy Mode Priority
The tenant override switch (unit or wall sensor mounted) can be used here to force the UVC into the Bypass Mode.
Typical operation is defined in this row of the table.
These are network variables.
Priority Result
Occupancy Occupancy Unoccupied
Effective
Override Input Sensor Input Input Signal
Occupancy
Output
Occupied Dont Care Dont Care Occupied
Unoccupied Dont Care Dont Care Unoccupied
Occupied Dont Care Occupied
Unoccupied Dont Care Bypass
Bypass
Contacts Open (Occupied) Occupied
Null (default)
Contacts Closed (Unoccupied) Bypass
Standby Dont Care Dont Care Standby
Occupied Dont Care Occupied
Unoccupied Dont Care Unoccupied
Null (default)
Contacts Open (Occupied) Occupied
Null (default)
Contacts Closed (Unoccupied) Unoccupied