TRACER CH532 Chiller controller User guide CG-SVU01B-E4
General information Foreword Reception These Installation Operation and Maintenance instructions are given as a guide to good practice in the installation, start-up, operation and periodic maintenance by the user of TRACER CH532 chiller controller. They do not contain the full service procedures necessary for the continued successful operation of this equipment. The services of a qualified service technician should be employed, through the medium of a maintenance contract with a reputable service company.
Contents Foreword 2 Warranty 2 Reception 2 General information 2 TRACER CH532 Presentation 4 Hardware architecture 5 Starting/stopping the unit 9 Menus 10 Display menu: “Data display” 11 Customer settings menu: “Settings” 12 Clock Setting menu: “Clock” 15 Unit configuration menu: “Configuration” 17 Alarms 22 Lon Talk option 25 Safety recommendations 32 Maintenance contract 32 Training 32 ® CG-SVU01B-E4 3
TRACER CH532 Presentation Important note: This document describes all the functions available on TRACER CH532 with software version 2.0 and explains how to program it. Certain parameters must only be modified by qualified personnel. Before changing any parameter, always check that the change does not affect the good and safe operation of the equipment. Operation must always stay in the catalogued limits.
Hardware architecture 10 11 Prg Esc 9 9 Figure 2 - TRACER CH532 inputs and outputs CG-SVU01B-E4 5
Hardware architecture Table 1 - TRACER CH532 General description Item 1 2 3 4 5 6 7 8 9 10 11 6 Description 24 V Power supply (G+,GO-) Yellow LED (Power on) Red LED (Alarm) Fuse (2A , 5x20) Universal Analog inputs: NTC,0/1V,0/10V,0/20mA, 4/20mA) Passive Analog Inputs (NTC,PT1000 , ON/OFF) Analog Outputs (0/10V) Digital Inputs (24Vac / Vdc) Digital Inputs (230Vac or 24Vac / Vdc) Relays digital output User interface Communication interface CG-SVU01B-E4
Hardware architecture Table 2 - Inputs and output summary list AI: Leaving water temperature sensor AI: Entering water temperature sensor AI: Ambient temperature sensor AI: Suction pressure circuit 1 - LP1 transducer AI: Suction pressure circuit 2 - LP2 transducer AI: Discharge pressure circuit 1 - HP1 transducer AI: Discharge pressure circuit 2 - HP2 transducer AI: External water setpoint reset (option) AI: Unused DI: Compressor C circuit 1 fault DI: Compressor C circuit 2 fault DI: Compressor A circuit 1
Hardware architecture TRACER CH532 offers customer the possibility to use inputs or outputs in order to: - use an external water setpoint reset using an analog input (refer to figure 3) - use an auxiliary setpoint - connect a remote on/off of the unit or a circuit - reset faults - connect a remote Cooling/Heating switch - return a circuit fault Note: External water setpoint Based on a external signal input, it will be possible to offset the active setpoint from 0°C to 20°C.
Starting/stopping the unit Once the unit is powered on (main disconnect switch closed) TRACER CH532 returns to the following display: TRACER CH532 01/05/04 Water Temp OFF BY KEYB. V2.0 00:00 20.0°C Note: In case of power failure unit will restart in the state (operating mode, setpoints…) it was in before the power failure and default screen will be displayed.
Menus TRACER CH532 allows the user to access 4 menus to display or adjust operation parameters: • “Data display” menu - This menu allows the user to visualize all operation parameters: - Water and air temperatures - Refrigerant pressures - Saturated refrigerant temperatures - Compressors status - Compressor running hours - Number of compressors starts - Unit operating mode - Compressors failures counters • “Settings” menu - This menu is password protected.
Display menu: “Data display” From the menu screen, select “Data Display” then press Pressing or will allow navigation from screen 1 to 8 as shown hereafter: The menu is looped making it possible to scroll from the first item in the menu to the last item. Lvg Wat Temp Ret Wat Temp Amb Temp Active StP 08.0°C 12.0°C 28.0°C 07.0°C 1.
Customer settings menu: “Settings” From the menu screen, select Cooling Stp = Cold water setpoint (-12 to 20°C - factory setting: 7°C) Heating Stp = Hot water setpoint (20 to 60°C - factory setting: 45°C) Aux Wat Stp = Auxiliary setpoint (-12 to 60°C - factory setting: 10°C) Aux Wat = Auxiliary setpoint from external source: Enable = Auxiliary setpoint validated Disable = Auxiliary setpoint nonvalidated “Settings” then press .
Customer settings menu: “Settings” 4. Operating mode Comp seq: Compressor sequencing To access one of the parameters displayed, press value using and change or .
Customer settings menu: “Settings” 7. Remote Mode To access one of the parameters displayed, press value using and change or . Confirm the value by pressing Chiller control Mode: Local Remote Local: Setpoints are entered on the module. Orders sent from the BMS are not taken into account. Remote: Orders sent from the BMS are taken into account.
Clock Setting menu: “Clock” From the menu screen, select “Clock” then press . Following screen will appear: User password 0000 Enter default password:”0000” (factory set) Press and cursor will move to first field of password. Pressing or will increment the value from 0 to 9999. Keeping pressure on or Press will move the numbers fast. to confirm password. 2. ON/OFF program type When enabled, this program will control the unit operation (On/Off).
Clock Setting menu: “Clock” 2.1 Weekly program To access one of the parameters To validate hourly zone program, press displayed, press and change value using and change or value using or . Confirm the value by . Confirm the pressing value pressing Program Hourly zone Program Weekly Start Stop Mon Fri Disable Start: Starting day Stop: Ending day Disable: No program Enable: Program used 2.2 Daily program To access one of the parameters 3.
Unit configuration menu: “Configuration” From the menu screen, select “Configuration” then press Following screen will appear: . User password 0000 Figure 5 - Single pump operation Note: figures 5 to 8, Unit Off means that the unit is stopped by keyboard or by an external contact On Enter default password:”0000” (factory-set) Press and cursor will move to first field of password. Pressing or On Pump will increment the value from Off t 0 to 9999. Keeping pressure on or will move the numbers fast.
Unit configuration menu: “Configuration” Figure 8 - Dual pump protection Pump 1 Pump protection input Pump 2 Fault reset Pump 1 Message 46* Message 46* Operation Enable/Disable Pump 2 Message 47* Pump 1 Pump control outputs Unit stopped (manual reset) Pump 2 * refer to “alarms” section for meaning of message 18 CG-SV01B-E4
Unit configuration menu: “Configuration” 2. Compressors timers To access one of the parameters 4. Control dead bands To access one of the parameters displayed, press displayed, press value using and change or . Confirm the value by pressing ACC 1st Start ACC On-On Min On-On Min Off-Off value using and change or .
Unit configuration menu: “Configuration” 6. Sensors and transducers To access one of the parameters displayed, press value using and change or . Confirm the 8. Analog Output (for speed inverter) Note: This screen is displayed only if “Invert” has been selected in the HP control menu (refer to §3) To access one of the parameters displayed, press value by pressing value using Temp probe Press probe Min Press Max Press NTC 4..20mA 0.0bar 30.
Unit configuration menu: “Configuration” 9. Operating limits (cooling) Low Amb Cooling Low Amb Limit CW High Limit CW High Limit On -10.0°C On 15.0°C 11. Defrost cycle termination To access one of the parameters 12. Compressor alarm To access one of the parameters displayed, press displayed, press value using and change or . Confirm the 10. Defrost demand setpoint Low Amb Heat StP Min Temp Defrost Max StP Max Temp -10.0°C 10.0°C 12.0°C 22.
Alarms 1. Alarms display and Resetting A fault on a unit will be shown through the user interface or through 2 digital outputs, one for each refrigerant circuit. The alarms are divided into 3 categories: - Warning. Shows that something is wrong on the unit but unit can be kept in operation. A message is displayed on the user interface screen. These messages are not recorded in the history list.
Alarms Table 4 - Status, warnings and alarm messages No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Message No Alarm Ext. Ckt1 Stop Ext. Ckt2 Stop User Ckt1 Stop User Ckt2 Stop Remote Ckt1 Stop Remote Ckt2 Stop Clock Unit Stop Operator Stop Ckt1 Defrost Ckt2 Defrost Warning Comp.1 Maintenance Warning Comp.2 Maintenance Warning Comp.3 Maintenance Warning Comp.
Alarms Table 5 - History events record No Message No History Air Sensor Reset Type Auto Auto Unit status Unit On Unit Off Water In Sensor Auto Unit On Water Out Sensor Auto Unit Off Lp Sensor Ckt1 Auto Circuit 1 Off Hp Sensor Ckt1 Auto Circuit 2 Off Lp Sensor Ckt2 Auto Circuit 1 Off Hp Sensor Ckt2 Auto Circuit 2 Off Fan Protection 1 Fan Protection 2 Lp Ckt1 fault Auto Auto Auto or Manual Unit On Unit On Circuit 1 Off Lp Ckt2 fault Auto or Manual Circuit 2 Off Low Water Temp Comp.
LonTalk® option Description The Lon interface uses an Echelon FTT-10 transceiver, which is approved to be used on the TP/FT-10 channel.
LonTalk® option LED meaning and function Green Status LED LED status LED is OFF continuously. Meaning/Function • Normal condition • Broken hardware • No power LED is ON.
LonTalk® option Nv1 0=off 1=on nv2 range -12.2°C 48.
LonTalk® option Cable characteristics Level 4 cable may be used with TP/FT-10 channels. The level 4 cable specification used by Echelon and as originally defined by the National Electrical Manufacturers Association (NEMA) differs from the Category 4 specification proposed by the Electronic Industries Association / Telecommunication Industries Association (EIA / TIA). The following specifications can be used by cable suppliers to identify a compliant Level 4 cable.
Notes CG-SV01B-E4 29
Notes 30 CG-SV01B-E4
Notes CG-SV01B-E4 31
Safety recommendations Maintenance contract Training To avoid accidents and damage, the following recommendations should be observed during maintenance and service visits: 1. The maximum allowable pressures for system leak testing on low and high pressure side are given in the chapter “Installation”. Always provide a pressure regulator. 2. Disconnect the main supply before any servicing on the unit. 3.