Use and Care Manual

TANKLESS WATER HEATER
C. ADJUSTING GAS PRESSURE AT THE WATER HEATER
1. The water heater and its individual shutoff valve must be disconnected from the gas supply piping sys-
tem during any pressure testing of the system at test pressures greater than ½ psi (3.5 kPa).
2. The water heater must be isolated from the gas supply piping system by closing its individual manual shutoff
valve during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ psi
(3.5 kPa).
The minimum and maximum inlet gas line pressures must meet the requirements shown in Table 16.
Do not fire (operate) the water heater until all connections have been completed and the heat exchanger is
filled with water. Doing so will damage the water heater and void the warranty.
D. SETTING AND VERIFYING THE COMBUSTION SETTING
1. After the appliance has fired, flip DIP switch seven (7) to the ON position (low fire). Proceed to check
appliance combustion values.
Table 15 – Gas Pressure Requirements
LP GAS NATURAL GAS
Minimum Pressure
8.0” WC
Minimum Pressure 3.5” WC
Maximum Pressure 13.0” WC
Maximum Pressure
10.5” WC
36
NOTE: Refer Figure 18 when adjusting gas pressure. Loosen the bolts before checking the
gas inlet pressure.
NOTICE
NOTE: Use a combustion analyzer to ensure CO and CO2 values are within the range shown in
Table 16.