System information

EAC-SF-13 Numbers in [brackets] are for 50 Hz international systems. 23
Service Facts
Component Failure Evaluation in 24 Volt Mode
Door panel has
yellow or red
flashing LEDs
Remove the
power door,
collection cells,
and field charger
Reinstall power
door to air cleaner
Power the air
cleaner with
24VAC and
establish a “G”
call from T-Stat
Bypass the 10 minute
time delay (This is
done by entering and
exiting the set-up
mode)
Wait 10 seconds
Door operates
correctly
Does Green Led #1
begin to flash slowly
Replace the
power door
NoYes
Turn power off,
Remove the power
door, install the
collection cells, and re-
install the power door
Replace both
collection cells
Air cleaner is
operating
correctly
The power door
and collection
cells operate
correctly
Wait 10 seconds
Replace the field
charger
Power the air
cleaner with
24VAC and
establish a “G”
call from T-Stat
Bypass the 10 minute
time delay (This is
done by entering and
exiting the set-up
mode)
Does Green Led #1
begin to flash slowly
Yes No
Turn power off,
Remove the power
door, install the field
charger, and re-install
the power door
Power the air
cleaner with
24VAC and
establish a “G”
call from T-Stat
Bypass the 10 minute
time delay (This is
done by entering and
exiting the set-up
mode)
Wait 10 seconds
Does Green Led #1
begin to flash slowly
Yes No