Operating instructions

6 Pub. No. 18-HE56D1-9
Installer's Guide
D. INSTALLATION GUIDELINES
Figure 15 Template
1. Identify the installation template from the upgrade kit
packaging. See Figure 15. Install the template onto
the air cleaner enclosure.
NOTE: The template must be pushed towards the back of
the air cleaner enclosure until the front flange of the
installation template is fully seated against the leading
edge on the enclosure. The template must also be pushed
towards the one inch U-channel rail as shown in Figure
16. If the template is improperly used, the filter
components will not fit into the air cleaner enclosure
correctly.
INSTALLATION OF THE FILTER MOUNT
RAILS
Remove all existing filters and PRE-FILTERs from the air
cleaner enclosure and discard.
PUSH
Two edges
align.
Figure 16
U-channel
rail
TFE MODELS ONLY
-
Remove Existing Electrical Hardware:
Identify the existing air cleaner located in the return air
duct of a central forced-air furnace/air handler. The air
cleaner is typically installed as shown in Figure 6.
FURNACE AND AIR HANDLER
- (120 VAC models):
If the existing air cleaner is an electronic type Perfect
Fit™ air cleaner filter (EAC), switch the POWER button
to the “OFF” position. All furnace applications, and
some air handler applications use 120 VAC 3 prong
power cord. This should be unplugged from the
electrical outlet.
AIR HANDLER
- (240 VAC models):
If the EAC is internally wired into the air handler, the
power cord and polarized connector adapter will need to
be removed from the air handler system.
1. Disconnect the strain relief connector. See Figure 14 to
the right.
2. Remove the six pin polarized connector on the adapter
located between the female polarized connector on the
heater and the male polarized connector from the air
handler control box. See Figure 14.
3. Reconnect the female polarized connector on the heater
and the male polarized connector from the air handler
control box.
4. Disconnect the green ground wire on the plug adapter
from the heater barrier.
5. Seal the knockout used by the previous power wires.
NOTE: For Non-TFE models, skip the section below and go
to the next page.
Figure 14 TFE Wiring
Electronic Air
Cleaner Cord
Control Box Plug
Connect Heater Cord
to the Control Box Plug
Remove Electronic Air Cleaner
“Polarized Connector Adapter”
Cord to the heater