Specifications

28 BAS-SVX36C-EN
Configuration
0140 Schedule options 1 0 Non-programmable
1 Programmable
0150 TOD/Economizer
output
(terminal A)
0 0 Unused
1 TOD energizes terminal A during occupied period, not during
unoccupied period.
2 Economizer energizes terminal A during a call for cool
0151 Heat fan
operation
0 0 System controls fan
1 Thermostat controls fan
0153 Reversing value
O/B
0 0 O/B terminal energized in cooling
1 O/B terminal energized in heating
0160 CPH 1st stage
compressor
(2)
3 1-5 Cycles per hour for 1st stage compressor - only for systems with cool or heat
pump stage - also changes 2nd stage cool default CPH
0161 CPH 2nd stage
compressor
(2)
3 1-5 Cycles per hour for 2nd stage compressor - only for systems with two cool or
heat pump stages
0162 CPH 1st stage
conventional
heat
(2)
5 1-10 Cycles per hour for 1st stage conventional heat - only for systems with heat
stages - also changes 2nd stage heat default CPH
0163 CPH 2nd stage
conventional
heat
(2)
9 1-10 Cycles per hour for 2nd stage conventional heat - only for systems with two
conventional heat stages
0164 CPH for auxiliary
heat
(2)
9 1-10 Cycles per hour for auxiliary heat - only for heat pump systems with more
heat than cool stages
0165 CPH for
emergency
heat
(2)
9 1-10 Cycles per hour for emergency heat - only for heat pump systems with more
heat than cool stages
0170 Continuous
backlight
0 0 Backlight “ON” time is limited
1 Backlight does not turn off
0180 Changeover 1 0 Manual changeover (heat/cool/off) - manually changeover the thermostat
between heat, cool, and off
1 Auto changeover (heat/cool/auto/off) - manually changeover between heat,
cool, and off, or select automatic changeover
0181 Deadband
(3)
3 2 2° F (1° C)
3 3° F (1.5° C)
4 4° F (2.0° C)
5 5° F (2.5° C)
6 6° F (3.0° C)
7 7° F (3.5° C)
8 8° F (4.0° C)
9 9° F (4.5° C)
0182 Minimum
compressor off
time
5 0-5 Minutes for compressor off time - for systems with cool or heat pump stages
- (Minutes specified here are added to the 5 min base off time.)
0190 Power supply
frequency
0 0 60Hz
1 50 Hz
0210 Temperature
sensor selection
0 0 Internal for H/C - display can show only local temperature and setpoint
1 Internal for H/C - remote (connected to S1 & S2)
(4)
for display - display can
show local and remote temperature, and setpoint
2 Internal for H/C, remote (connected to S1 & S2)
(4)
for compressor and
auxiliary lockout; display can show local and remote temperature, and
setpoint - (Disabled for conventional systems.)
3 Remote (connected to S1 & S2)
(4)
for H/C, internal disabled; display can show
remote indoor temperature and setpoint
Table 6. Installation Options for 3-Heat/2-Cool Programmable Thermostat (continued)
No. Name Default Opts. Descriptions