Specifications

BAS-SVX36C-EN 27
Configuration
5. Press , ,or to scroll through the options, identified by their numbers, until you reach
the option you want to change:
scrolls to a lower-numbered option.
or scrolls to a higher-numbered option.
6. Use
or to change the value of the option:
decreases the value.
increases the value.
7. Repeat Step 5 and Step 6 until you have made all necessary changes.
Note: V
alues are saved in permanent memory after setting a value and moving to next
configuration parameter, and also when you exit configuration mode.
8. Do one of the following to exit configuration mode:
Remove the thermostat cover, if necessary, and then press and immediately release the
configuration button.
Do not press any buttons for 10 min.
Press and hold for 2 sec.
Table 6. Installation Options for 3-Heat/2-Cool Programmable Thermostat
No. Name Default Opts. Descriptions
0100 Temperature
indication/
resolution
0 0 °F, 1 degree resolution
1 °F, 0.5 degree resolution
2 °C, 1 degree resolution
3 °C with 0.5 degree resolution
4 °C with 0.1 degree resolution
0110 Clock format 12 12 12 hour clock
24 24 hour clock
0120 Year 09 09-99 2009 - 2099
0121 Month 1 1-12 Months of the year
0122 Day 1 1-31 Days of the month
0125 Daylight savings 2 0 Disabled
1 US (1987), changeover at 2:00am
2 US (2007), changeover at 2:00am
3 Europe, changeover at 1:00am
4 Manual, changeover at 2:00am
0126 Spring month
(1)
03 01-12 The month in which the Spring daylight savings change occurs
0127 Spring day 08 01-31 The day on which the Spring daylight savings change occurs
0128 Fall month 11 01-12 The month in which the Fall daylight savings change occurs
0129 Fall day 08 01-31 The day on which the Fall daylight savings change occurs
0130 System selection 8 1 1H/1C (conv) 1st Stage Heat (W), 1st Stage Comp (Y), Fan (G)
2 1H/1C (HP) 1st Stage Comp (Y), Changeover (O/B), Fan (G)
3 1H (Conv) 1st Stage Heat (W), without fan
4 1H (Conv) 1st Stage Heat (W), Fan (G)
5 1C (Conv) 1st Stage Comp (Y), Fan (G)
6 2H/1C (HP) 1st Stage Comp (Y), Changeover (O/B), Auxiliary Heat (W1),
Fan (G)
7 2H/2C (Conv) 1st & 2nd Stage Heat (W,W2), 1st & 2nd Stage
Comp (Y,Y2), Fan (G)
8 2H/1C (Conv) 1st & 2nd Stage Heat (W,W2), 1st Stage Comp (Y), Fan (G)
9 1H/2C (Conv) 1st Stage Heat (W), 1st & 2nd Stage Comp (Y,Y2), Fan (G)
10 2H/2C (HP) 1st & 2nd Stage Comp (Y,Y2), Changeover (O/B), Fan (G)
11 3H/2C (HP) 1st & 2nd Stage Comp (Y,Y2), Changeover (O/B), Auxiliary
Heat (W1), Fan (G)